6
Installation opening dimensions (see Fig. 9-11)
Examples of fire damper installing
The fire damper can be integrated into a solid wall construction made e.g. of normal concrete/
masonry, porous concrete with minimum thickness 100 mm or into solid ceiling construction made
e.g. of normal concrete with minimum thickness 110 mm or porous concrete with minimum
thickness 125 mm.
The fire damper can be integrated into a gypsum wall construction with fire classification
EI 120 or EI 90.