54
Horizontal installation
Fire dampers can be suspended by using threaded rods and a mounting profiles. Load the suspension
system depend on weight of the fire damper.
Damper assembly procedures must be done so as all load transfer from the fire separating construc-
tions to the damper body is absolutely excluded. Back-to-back air-conditioning piping must be hung or
supported so as all load transfer from the back-to-back piping to the damper is absolutely excluded.
Threaded rods longer than 1,5 m require fire-resistant insulation.
Threaded rod fixing to the ceiling construction - see fig. 60
Vertical installation
Fire dampers can be suspended by using threaded rods and a mounting profiles. Load the
suspension system depend on weight of the fire damper.
Damper can be suspended from the ceiling construction or supported above the ceiling construc-
tion. Damper assembly procedures must be done so as all load transfer from the fire separating
constructions to the damper body is absolutely excluded. Back-to-back air-conditioning piping
must be hung or supported so as all load transfer from the back-to-back piping to the damper is
absolutely excluded.
Threaded rods longer than 1,5 m require fire-resistant insulation.
Position:
1
Fire damper
2
Damping pad
3
Extension piece
4
Threaded rod
5
Suspension ring
Examples of using materials: