64
Spare parts are supplied only on basis of an order.
Control for square damper and round damper is identical.
If fuse Tf1 is initiated (duct outside temperature) than is necessary to change thermoelectrical
starting mechanism BAT72B-S. Whereas is initiation temperature higher than actuator
mechanism operating temperature +50°C, recommended actuating mechanism manufacturer
make complete revision or change actuating mechanism and thermoelectrical starting mechanism.
If fuses Tf2/Tf3 are initiated (duct inside temperature) than is possible change only part ZBAT72
or ZBAT95 (according initiating temperature).
Data label is placed on the damper body.
Certifikace: 1391-CPD-0114/2012
SERIAL NUMBER:
SIZE:
WEIGHT (kg):
DESIGN:
Hostomice 550
Czech Republic
CLASSIFICATION: EI 90 (ve ho i o) S
FIRE DAMPER FDMA-S
MANDÍK, a.s.
267 24 Hostomice
TPM018/01
12
EN 15650:2010
1391
Summary of Contents for FDMA
Page 1: ......