40
TPM 075/09
POSITION:
1
Fire damper FDMB
2
Stuffing box (mineral stone wool min. density 140 kg/m )
3
Fire protection mastic min. thickness 1 mm
4
Cement lime plate min. thickness 15 mm (min. density
870 kg/m )
5
Stone wool bound with use of an organic resin with
crushed stone as a refrigerant (min. density 300 kg/m ),
EIS 90, thickness 60 mm
6
VRM-III***
7
Profil U25x40x25
8
Duct
Used materials - example*:
2 - Promapyr, Rockwool Steprock HD
3 - Promastop - P, K
4 - Promatect - H
5 - Rockwool Conlit Ductrock EIS 90, thickness 60 mm
* Stuffing box, fire protection mastic, cement lime plate and
insulation materials can be replaced by another approved
fire sealing system for damper installation with equivalent
material properties
** Dependent on the distance between damper and fire
separating construction
*** Reinforcement fixing VRM-III see Fig. 44
Fig. 52 Installation outside of solid wall construction
3
3
3
3
4
2
Min. 50
8
5
1
L=Min. 100
T=120
7 6
L=Min. 400
T=120
L=variable**
T=60
POSITION:
1
Fire damper FDMB
2
Stuffing box (mineral stone wool min. density 140 kg/m )
3
Fire protection mastic min. thickness 1 mm
4
Cement lime plate min. thickness 15 mm (min. density
870 kg/m )
5
Stone wool with one side stitched wire fencing (min.
density 105 kg/m ).
6
Duct
Used materials - example*:
2 - Promapyr, Rockwool Steprock HD
3 - Promastop - P, K
4 - Promatect - H
5 - Rockwool Wired Mat 105 thickness 3x60 mm
* Stuffing box, fire protection mastic, cement lime plate and
insulation materials can be replaced by another approved
fire sealing system for damper installation with equivalent
material properties
** Dependent on the distance between damper and fire
separating construction
3
3
3
3
4
2
Min. 50
6
5
1
L=Min. 100
D=240
L=Min. 400
D=240
L=variable**
D=180