8
TPM 092/13
Fig. 12 Communication and Control Device BKS 24-9A
3.2.
BKS 24-1B communication and control device is used for control and checks of fire dampers with
the BLF 24-T-ST actuating mechanism in conjunction with the BKN 230-24 supply and
communication device. BKS 24-1B receives information about the situation of the fire damper
through the BKN 230-24 supply and communication device and issues controlling commands.
The device is intended for building in into the distribution board. Light diodes on the front side of
the device signalise the operating situations of the damper and breakdowns of the whole system.
Nonpotential auxiliary contacts enable connection to the master control system (signalisation of
the damper position, failure reports, release of the ventilators etc.).
Tab. 3.1.1. BKS 24 -9A contacts K1 and K2
K1 Function Contact
Situation
State
Current Failure
15 16
No Failure
15 16
Programming K2 Auxiliary Contact
Function
Interconnection
State
K2 contact is on if all the
damperss are open
14 11
17 18
K2 contact is on if the damper
No. 1 is open
14 12
K2 contact is on if all the
dampers are closed
14 open
Function check can be done in the position OPERATION by means of pushing the TEST button.
While the button is pushed, the flap blade is turning into the position FAILURE. Fault function is
indicated by a report "FAILURE".
2
Tab. 3.2.1. Communication and Control Device BKS 24-9A
Communication and Control Device
BKS 24-9A
Nominal voltage
AC 24 V 50/60Hz
Power consumption
3,5 W (operating position)
Dimensioning
5,5 VA
Protection Class
III (safe small voltage)
Degree of protection
IP 30
Ambient Temperature
0
+ 50 °C
Connection
Terminals for conductor 2 x 1,5 mm