background image

9

1.)  All fire dampers has to be closed during installation process.

2.) The control mechanism has to be protected (covered) against damage and pollution during installation
 

process.

3.) Min. gap for installation (installation opening) is 25 mm (circular dimension

Ø

D + 50 mm).

4.) Installation gap  must  be  filled  by  approved  material  perfectly  in  all  the  installation  space  volume
 

(installation gap).

5.)

The  distance  between  the  fire  damper  and  the  construction  (wall,  ceiling)  must  be  minimum  75  mm

according  to  EN  1366­2.  In  case  that  two  or  more  dampers  are  supposed  to  be  installed  in  one  fire
separating construction, the distance between the adjacent dampers must be at least 200 mm according
to EN 1366­2 paragraph 13.5.

6.) Installation openings.

Summary of Contents for FDMD

Page 1: ......

Page 2: ...per installation 1 Fire damper FDMD 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper installation 3 Fire protection mastic Promastop P K or equ...

Page 3: ...identique syst me approuv avec les propri t s correspondantes 3 Protection coupe feu Promastop P K ou un quivalent ad quat paisseur minimum 1 mm 1 Clapet FDMD 2 Plaque r sistante au feu 3 Protection...

Page 4: ...y 800 kg m or another approved fire sealing system for damper installation 1 Fire damper FDMD 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper...

Page 5: ...cifique minimum 800 kg m 1 Clapet FDMD 2 Laine min rale de poids sp cifique minimum 140 kg m ou identique syst me approuv avec les propri t s correspondantes 3 Protection coupe feu Promastop P K ou u...

Page 6: ...ffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper installation 3 Fire protection mastic Promastop P K or equal min thickness 1 mm 1 Fire damper FDMD...

Page 7: ...e de poids sp cifique minimum 140 kg m ou identique syst me approuv avec les propri t s correspondantes 3 Protection coupe feu Promastop P K ou un quivalent ad quat paisseur minimum 1 mm 1 Clapet FDMD...

Page 8: ...7...

Page 9: ...8...

Page 10: ...Installation gap must be filled by approved material perfectly in all the installation space volume installation gap 5 The distance between the fire damper and the construction wall ceiling must be mi...

Page 11: ...positions dans des cloisons coupe feu verticales et horizontales 4 L espace entre le clapet et la cloison doit tre totalement rempli par une mati re ignifuge 5 La distance entre le clapet coupe feu et...

Page 12: ...openings in the wall Damper assembly procedures must be done so as all load transfer from the fire separating constructions to the damper body is absolutely excluded Back to back air conditioning pip...

Page 13: ...ts coupe feu et la cloison Les passages pour l installation des clapets coupe feu doivent tre r alis s de telle mani re ce que toute transmission de charge du b timent au clapet soit limin e Le condui...

Page 14: ...ot grind on the damper body during opening or closing 10 To provide needed access space to the control device all other objects must be situated at least 350 mm from the control parts of the damper In...

Page 15: ...et enlever le couvercle 9 Le corps du clapet ne doit pas se d former lors de l installation Apr s l installation du clapet la lame du clapet ne peut pas frotter contre le corps du clapet pendant la fe...

Page 16: ...st be carried out Check of thermal protective fuse and closing mechanism Push initiation lever lock OPEN to release the control lever and check its displacement into the position CLOSED Closing must b...

Page 17: ...re orifice de la plaque de base ou en utilisant un ressort diff rent Le changement de position de la lame du clapet en position OUVERT se fait par le proc d suivant En appuyant sur le ressort de bloca...

Page 18: ...17...

Page 19: ...18...

Page 20: ...19 MAND K a s Dob sk 550 26724 Hostomice esk Republika Tel 420 311 706 706 Fax 420 311 584 810 311 584 38 E Mail mandik mandik cz www mandik com...