11
8.
The fire damper can be integrated into a solid or gypsum wall construction or into solid ceiling
construction. Damper blade has to be inside of construction (labelled with BUILD IN EDGE on the
damper body).
7.) Placement of the openings in the wall.
Damper assembly procedures must be done so as all load transfer from the fire separating constructions to
the damper body is absolutely excluded. Backtoback air conditioning piping must be hung or supported
so as all load transfer from the backtoback piping to the damper is absolutely excluded.