Fire damper - FDMQ
Page 18
Version 2023-07-27
TPM 103/14
Function contact K1
Programming K2 Auxiliary Contact
situation
state
function
interconnection
state
current failure
K2 contact is on if all dampers are open
no failure
K2 contact is on if damper No. 1 is open
K2 contact is on if all dampers are closed
17
18
14
11
15
16
14
12
15
16
14 open
Communication and control device BKS 24-9A
Communication and control device BKS 24-9A
Nominal voltage
AC 24 V 50/60Hz
Power consumption
3,5 W
Dimensioning
5,5 VA
Protection Class
III
Degree of protection
IP 30
Ambient temperature
0°C … +50°C
Connection
terminal 2 x 1,5 mm
2
■
BKS 24-9A communication and control device is used for group
control and checks of 1 to 9 fire dampers with the actuator BF
24-TN-ST (BFL 24-T-ST, BFN 24-T-ST) in connection with the supply
and communication device BKN 230-24.
■
Signalisation of the damper position is individual; the damper can
be controlled and tested only as a group.
■
BKS 24-9A is intended for use in the distribution board and
displays the operation situations and failure reports of the
connected fire dampers.
■
It is possible to signalise functions such as the damper position
and failure reports or to transmit them further to the system by
means of integrated auxiliary switches.
■
BKS 24-9A receives signals from BKN 230-24 through the two-
conductor wiring and issues control commands.
Proper damper operation is indicated by two light LED diodes:
■
Control ON = position OPERATION
■
Control OFF = position FAILURE
■
If the fire damper do not reach the given position in time tolerable
for displacing, the appropriate light diode FAILURE starts to flash
and
K1
contact is opened (current failure).
■
In case that the faulty damper finally reaches its given position,
K1
is closed and the failure report light shines (the failure is saved in
memory).
■
K2
- the auxiliary contact - is used for signaling of the damper
blade position to the master device.
■
Function of this auxiliary contact can be programmed through the
terminal 14.
■
Function check can be done in the position OPERATION by means
of pressing the TEST button.
■
While the test button is pressed, damper blade is rotating into the
position FAILURE.
■
Fault function is indicated by a report "FAILURE".
■
Assembly and connection BKS 24-9A can be made by DIN 35 mm
panel. It is connected by two 9-pole plug-in connectors.