9
BKS 24-1B communication and control device is used for control and checks of fire dampers with
the BFL 24-T-ST actuating mechanism in conjunction with the BKN 230-24 supply and
communication device. BKS 24-1B receives information about the situation of the fire damper
through the BKN 230-24 supply and communication device and issues controlling commands.
The device is intended for building in into the distribution board. Light diodes on the front side of
the device signalise the operating situations of the damper and breakdowns of the whole system.
Potentialless auxiliary contacts enable connection to the master control system (signaling of the
damper position, failure reports, release of the ventilators etc.).
While a flashing green LED pilot light signalises damper blade motion towards the given position,
the same pilot light reports reaching the required position when shining constantly. If the flap
blade, with respect to the given time, does not reach the required position, then a red LED pilot
light starts to flash and at the same time, the failure contact is active. Once the damper blade
reaches the given position, this contact is deactivated. The LED pilot light keeps flashing unless
the failure is unblocked by means of the RESET button. Except for reporting failures, other three
auxiliary contacts are available. Contacts showing operating and failure position of the damper
are active when the damper is in the given position. Function check can be done by pressing and
holding the button "RESET/TEST" for longer time. While holding the button, the damper blade
moves in the direction of the failure position. Fault function is indicated by the LED pilot light.
BKS 24-1B can be connected by means of ZSO-11 11 pole connector for DIN 35 mm panel.
4
7
8
2
10
1
5
9
an insulation
transformer
~
damper position
breakdown
Notice: Relay contacts are drawn
without power
11
b
a
2-conductor wiring
to BKN230-24
Control
on /off
Reset
Test
External buton
optional
be interchanged
6
3
AC
24V
damper position
operation
Reset
Test
open
closed
alarm
failure
Connection through
conection can
not available
, starting with switching AC 24 on or pressing
«Reset/Test» button
possible cause: • short circuit or interruption of 2-conductor wiring
or damper failure (at BKN..) • Power supply AC 230V missing • defective
thermoelectrical starting • smoke detector activated • exceeded operation time
• Fault in system signalled, system check should be
done
Damper (drive) turning into
of breakdown position
Damper (drive) in
Damper (drive) turning into
of operating position
Damper (drive) in
light diodes
contacts
Description
Cause/Course
state
open
closed
alarm
closed
flashing
6
3
6
3
6
7
6
4
6
4
6
3
6
3
6
7
switched
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
open
open
open
open
open
open
flashing
flashing
• damper blocked