The  damper  bodies  are  usually  supplied  in  galvanised  sheet  metal  without  further  surface
treatment, alternatively with a special paint Alesta® AS AS3040-7403627 (RAL 7035-GL LIGHT

GREY) with a max. total thickness coating 120 ± 20μm, or the body can be completely made of

class  AISI  304,  possibly  AISI  316L  stainless-steel  sheet.  The  damper  leaves  are  made  of
asbestos-free fire-resistant boards made of Promatect-H or Promatect-MST. The control damper
devices  are  supplied  in  a  class  AISI  304  or  AISI  316L  stainless-steel  material  without  other
surface treatments. The main torsion spring in the mechanics is galvanised.

 

Thermal fuses are made of 0.5 mm thick brass sheet. The connecting material is galvanised, the
moving parts are made of class AISI 304 or AISI 316 stainless-steel.

 

All moving parts in the damper are conductively connected to the frame, the damper body.

 

• company logo - manufacturer  

• fire resistance 

• serial number

 

• company name and registered office  

• type and design 

• year of manufacture

 

• number of technical conditions /TPM/  

• size and weight 

• certification

 

Furthermore, there is a sign of damper non-explosivity on the damper.

 

The dampers are delivered as bulk cargo. Any other packing methods must be agreed with the
manufacturer  in  advance.  The  potential  packages  will  be  considered  non-returnable  and  their
price will not be included in the product price.

 

The  dampers  are  transported  by  box  freight  vehicles;  no  sharp  shocks  must  occur  and  the
ambient temperature must not 40°C. For handling during transport, the dampers must
be  protected  against  mechanical  damages  and  weather  impact.  If  the  customer  wishes  it,  the
dampers  can  be  transported  on  pallets.  During  transport,  the  damper  blade  must  be  in  the
"CLOSED" position.

 

Unless  another  method  of  reception  is  specified  in  the  purchase  order,  the  handover  of  the
dampers to the forwarder shall be understood as reception.

 

The dampers must be stored in covered buildings, in an environment without aggressive vapours,
gases and dust. A temperature in a range of -5°C and +40°C and a relative humidity of max. 80%
must be maintained in the buildings.

 

For handling during storage, the dampers must be protected against mechanical damage.

The scope of delivery includes a complete damper and a certificate of quality and completeness
with a stamp of inspection (the certificate is attached to the invoice).

 

The warranty for fire dampers provided by the manufacturer becomes completely null and void
after  any  unprofessional  handling  by  untrained  workers  (see  Article  10.1.),  when  dismantling
electrical  components,  i.e.  limit  switches,  actuators  and  thermoelectric  starting  devices.  The
warranty  also  becomes  null  and  void  if  the  dampers  are  used  for  purposes,  equipment  and
working conditions other than those permitted by these technical conditions or after mechanical
damage during handling.

 

If the dampers are damaged by transport, it is necessary to draft a report with the carrier upon
acceptance for the possibility of a later complaint.

Summary of Contents for FDMR

Page 1: ......

Page 2: ...cription 3 2 Design 3 3 Placement and Assembly 4 4 Dimensions 6 5 Electrical elements wiring diagram 11 6 Material surface protection 12 7 Product data 12 8 Logistic terms 12 9 Warranty 12 10 Installa...

Page 3: ...designed for environments protected against weather conditions with climatic conditions in 3K5 class with temperature limitation 20 C to 50 C without condensation icing ice formation without water an...

Page 4: ...damper using the button on the temperature sensor simulates fuse failure Using a special key supplied with the actuator the damper leaf can be manually adjusted to any position and the position secure...

Page 5: ...closing Fire damper Damper blade Fire dividing construction Fire damper Damper blade Fire dividing construction Protected duct Fire damper Damper blade Fire dividing construction The fire damper can b...

Page 6: ...ExPro TT 2 Body 2 damper 9 Inspection hole covering 3 Damper blade 10 Control lever 4 Electrical actuator Schischek ExMax 15BF 11 Pin with lever 5 Mechanical actuator Atex 12 Initiation button 6 Therm...

Page 7: ...ExPro TT 2 Body 2 damper 9 Inspection hole covering 3 Damper blade 10 Control lever 4 Electrical actuator Schischek ExMax 15BF 11 Pin with lever 5 Mechanical actuator Atex 12 Initiation button 6 Therm...

Page 8: ...Thermo electrical fuse ExPro TT 2 Damper blade 8 Inspection hole covering 3 Electrical actuator Schischek ExMax 15BF 9 Control lever 4 Mechanical actuator Atex 10 Pin with lever 5 Thermal fuse 11 Ini...

Page 9: ...Thermo electrical fuse ExPro TT 2 Damper blade 8 Inspection hole covering 3 Electrical actuator Schischek ExMax 15BF 9 Control lever 4 Mechanical actuator Atex 10 Pin with lever 5 Thermal fuse 11 Ini...

Page 10: ...side length 1000 mm FDMQ from 150x150 to 1500x800 FDMR from 100 to 800 mm FDMA PM 900 and 1000 Square damper flanges with a width of 30 mm are provided with oval holes in the corners The connection di...

Page 11: ...e 21 a 22 Adjustment time drive reverse gear 30 s 10 s Ambient operating temperature Storage temperature 40 C 40 C at T6 40 C 50 C at T5 40 C 70 C Humidity 0 95 rH non condensing Connection optional a...

Page 12: ...box freight vehicles no sharp shocks must occur and the ambient temperature must not exceed 40 C For handling during transport the dampers must be protected against mechanical damages and weather imp...

Page 13: ...the AUTHORISED PERSON themselves directly with the trainer Upon the expiry of the validity of the CERTIFICATE it loses its validity and is excluded from the trainer s registration Only professionals...

Page 14: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Reviews: