background image

4

with ExPro-TT thermoelectric activation device

(hereinafter only actuator).

 

After connection to supply 230V AC or 24V AC/DC the actuator moves the damper leaf to the
"OPEN" operating position and at the same time biases its return spring. As long as the actuator
is energised, the damper leaf is in the "OPEN" position and the return spring is preloaded. The
time for completely opening the damper leaf from the "CLOSED" position to the "OPEN" position
is  approximately  30  sec.  If  the  actuator's  power  supply  is  interrupted  (loss  of  supply  voltage,
activating the temperature sensor or by pressing the reset button on the temperature sensor), the
return spring moves the damper leaf to the emergency position "CLOSED. The time for moving
the leaf from the "OPEN" position to the "CLOSED" position is approximately 10 sec. If the supply
voltage is restored (the leaf can be in any position), the actuator starts moving the damper leaf
again  to  the  "OPEN"  position,  but  only  if  the  temperature  sensor  has  not  been  activated.  The
sensor's temperature activation occurs when the temperature e72°C. Then the supply
voltage  is  permanently  and  irrevocably  interrupted  and  the  actuator  moves  the  damper  leaf  to
emergency "CLOSED" position by means of a pre-loaded return spring.

  a) by interrupting and re-applying the supply voltage, e.g. by a signal from the EFS.

  b) directly on the built-in damper using the button on the temperature sensor (simulates fuse failure).

 

Using a special key (supplied with the actuator), the damper leaf can be manually adjusted to any
position  and  the  position  secured.  Unlocking  is  done  manually  with  a  key  or  automatically  by
applying the supply voltage.

manual and temperature (ZONE 1, 2)

.02

II 2G

manual and temperature with limit switch ("CLOSED") (ZONE 1, 2)

.12

II 2G

with actuator ExMax-15- BF AC 230V, with thermoelectric activation
ExPro-TT equipment (ZONE 1, 2)

.42

II 2G

with actuator ExMax-15- BF AC/DC 24V, with thermoelectric activation
ExPro-TT equipment (ZONE 1, 2)

.52

II 2G

Manual and thermal with two limit switches ("OPEN", "CLOSED") (ZONE 1, 2)

.81

II 2G

 

Fire  dampers  are  suitable  for  installation  in  vertical  and  horizontal  passages  of  fire  dividing
structures.  Penetrations  regarding  damper  installation  must  be  done  in  such  a  way  that  the
transfer of all loads from the fire dividing structures to the damper body is completely excluded.
The adjoining air duct must be suspended or supported in such a way that load transfer from the
adjoining duct to the damper flange is completely ruled out.

 

To ensure the necessary space for access to the control device, it is recommended that other
objects be at least 350 mm away from the control parts of the damper. At least one inspection
opening must be accessible.

 

The distance between the fire damper and the structure (wall, ceiling) must be at least 75 mm. If
two  or  more  dampers  are  to  be  installed  in  one  fire  dividing  structure,  the  distance  between
adjacent dampers must be at least 200 mm.

Summary of Contents for FDMR

Page 1: ......

Page 2: ...cription 3 2 Design 3 3 Placement and Assembly 4 4 Dimensions 6 5 Electrical elements wiring diagram 11 6 Material surface protection 12 7 Product data 12 8 Logistic terms 12 9 Warranty 12 10 Installa...

Page 3: ...designed for environments protected against weather conditions with climatic conditions in 3K5 class with temperature limitation 20 C to 50 C without condensation icing ice formation without water an...

Page 4: ...damper using the button on the temperature sensor simulates fuse failure Using a special key supplied with the actuator the damper leaf can be manually adjusted to any position and the position secure...

Page 5: ...closing Fire damper Damper blade Fire dividing construction Fire damper Damper blade Fire dividing construction Protected duct Fire damper Damper blade Fire dividing construction The fire damper can b...

Page 6: ...ExPro TT 2 Body 2 damper 9 Inspection hole covering 3 Damper blade 10 Control lever 4 Electrical actuator Schischek ExMax 15BF 11 Pin with lever 5 Mechanical actuator Atex 12 Initiation button 6 Therm...

Page 7: ...ExPro TT 2 Body 2 damper 9 Inspection hole covering 3 Damper blade 10 Control lever 4 Electrical actuator Schischek ExMax 15BF 11 Pin with lever 5 Mechanical actuator Atex 12 Initiation button 6 Therm...

Page 8: ...Thermo electrical fuse ExPro TT 2 Damper blade 8 Inspection hole covering 3 Electrical actuator Schischek ExMax 15BF 9 Control lever 4 Mechanical actuator Atex 10 Pin with lever 5 Thermal fuse 11 Ini...

Page 9: ...Thermo electrical fuse ExPro TT 2 Damper blade 8 Inspection hole covering 3 Electrical actuator Schischek ExMax 15BF 9 Control lever 4 Mechanical actuator Atex 10 Pin with lever 5 Thermal fuse 11 Ini...

Page 10: ...side length 1000 mm FDMQ from 150x150 to 1500x800 FDMR from 100 to 800 mm FDMA PM 900 and 1000 Square damper flanges with a width of 30 mm are provided with oval holes in the corners The connection di...

Page 11: ...e 21 a 22 Adjustment time drive reverse gear 30 s 10 s Ambient operating temperature Storage temperature 40 C 40 C at T6 40 C 50 C at T5 40 C 70 C Humidity 0 95 rH non condensing Connection optional a...

Page 12: ...box freight vehicles no sharp shocks must occur and the ambient temperature must not exceed 40 C For handling during transport the dampers must be protected against mechanical damages and weather imp...

Page 13: ...the AUTHORISED PERSON themselves directly with the trainer Upon the expiry of the validity of the CERTIFICATE it loses its validity and is excluded from the trainer s registration Only professionals...

Page 14: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Reviews:

Related manuals for FDMR