13
Gypsum wall construction
Spiral pipe
Fire resistant fill (for recommended materials see separate table)
Threaded rod and anchor to the wall (or ceiling) (e.g. threaded rod M8 and anchor type according pipe weight)
Fire protection mastic min. thickness 1mm (e.g. PROMASTOP-P or K)
Fire damper FDMS
Anchor for damper collar (threaded rod and nuts M8 or e.g. anchor FISCHER - type KD8)
Fixing part of the pipe between wall and pipe (only recommended)
Hanging ring (e.g. FISCHER - type LGS)
View B:
Ø
D
Fire classification:
≥
100
Connecting surface between damper collar
and wall fulfil with fire resistant sealant before
instalation of the damper (recommended type
of sealant - e.g. PROMAT K84 or HILTI CFS-S)
Summary of Contents for FDMS Series
Page 1: ......
Page 12: ...11 Fire classification 96 47 47 96 96...
Page 15: ...14 Fire classification 96 47 47 96 96...
Page 18: ...17 Fire classification 96 47 47 96 96...
Page 29: ...28...
Page 30: ...29...
Page 31: ...30...