10
TPM 109/15
3.1.
BKSE24-6 indicates operating status and fault signals for the smoke extraction dampers. The
auxiliary contacts that are incorporated also allow functions to be signaled or passed on to
higherlevel control systems. The signals from the BKNE230-24 unit are received by the
BKSE24-6 unit and evaluated individually. All BKNE230-24 units are triggered simultaneously. To
BKSE24-6 can be connected max. 6 BKNE230-24.
Communication is via the 2-wire conductor. Correct operation of the dampers is indicated by
means of two LEDs. The operating status of the SBSE-Control system and any faults are also
indicated by this LED and the corresponding fault LED.
The BKSE24-6 unit can be clipped directly to a 35 mm DIN mounting rail and connected by means
of two 9-pole plug-in terminals.
3. Communication and control devises
Tab. 3.1.1.
Communication and control devices BKSE 24-6
Communication and control devices
BKSE 24-6
Nominal voltage
AC 24 V 50/60Hz
Power consumption
3,5 W (operating position)
Dimensioning
5,5 VA 18 VA (Imax 6.4 A @ 2.5 ms)
Protection class
III
Degree of protection
IP 20
Ambient temperature range
0 … + 50 °C
Connecting
screw terminals for cable 2x1,5 mm
2
Tab. 2.1.2.
Elektromagnet EM230
Elektromagnet EM230
Jmenovité nap
ě
tí
AC 230 V / 50 Hz
Zátahový proud
1,2 A
Krytí
IP 40
Teplota okolí provozní
-10 °C … +40 °C
P
ř
ipojení
kabel 1m, 3x0,75mm
2
Obr. 15 Elektromagnet EM230