  Check of damper blade displacement can be realize after actuating mechanism supply connec-

tion  or  signal  connection  from  higher  level  control  systems.  Blade  displacement  from  position
“OPEN” to position “CLOSED”  and return displacement is checked.

 

Before entering the dampers into operation after assembly and after sequential revisions, checks
and  functionality  tests  of  all  designs  including  operation  of  the  electrical  components  must  be
successfully provided and finished.

 After entering into operation, these revisions must be done

according to requirement set by national regulations.

  In case that dampers are found unable to serve for their function for any cause, it must be clearly

marked. The operator is obliged to ensure that the damper is put into condition in which it is ready
for function and meanwhile he is obliged to provide the fire protection by another appropriate way.

  Results of regular checks, imperfections found and all-important facts connected with the damper

function must be recorded in the "FIRE BOOK" and immediately reported to the operator.

 

Before entering the dampers into operation after their assembly and by sequential checks, the
following checks must be carried out for all designs.

  Visual  inspection  of  proper  damper  integration,  inside  damper  area,  damper  blade,  contact

surfaces and silicon sealing.

 

Spare parts are supplied only on basis of an order.

Summary of Contents for SEDS-L

Page 1: ......

Page 2: ...for production designing ordering delivery maintenance and operation 1 Description 2 2 Design 3 3 Dimensions weights 8 4 Placement and Assembly 10 5 Pressure drops 12 6 Noise data 12 7 Material 14 8...

Page 3: ...applications according with EN 1366 9 The field of direct applications based on tests results is acceptable according to EN 1363 1 part A 1 and A 2 EN 1366 2 part 13 and EN 1366 10 part 9 Smoke extrac...

Page 4: ...r macroclimatic areas with mild climate according to EN 60 72133 Temperature in the place of installation is permitted to range from 20 C to 50 C Design with actuating mechanism SEDS L is equipped by...

Page 5: ...II II Degree of protection IP 54 Running time for 95 30 s Ambient temperature range Non operating temperature 30 C 50 C 40 C 80 C Connecting motor auxiliary switch cable 1 m 3 x 0 75 mm cable 1 m 6 x...

Page 6: ...imensioning 18 VA Imax 8 2 A 5 ms 15 VA Imax 7 9 A 5 ms Protection class III II Degree of protection IP 54 Running time for 95 60 s Ambient temperature range Non operating temperature 30 C 50 C 40 C 8...

Page 7: ...the BKSE24 6 unit It also receives positioning commands from the control unit and triggers the actuator to the required position The last control command is retained troughout temporary power failure...

Page 8: ...ed by the BKSE24 6 unit and evaluated individually All BKNE230 24 units are triggered simultaneously To BKSE24 6 can be connected max 6 BKNE230 24 Communication is via the 2 wire conductor Correct ope...

Page 9: ...consumption 3 5 W operating position Dimensioning 5 5 VA 18 VA Imax 6 4 A 2 5 ms Protection class III Degree of protection IP 20 Ambient temperature range 0 50 C Connecting screw terminals for cable 2...

Page 10: ...BE 5 44 5 0 3075 BE 5 38 5 0 1785 BE 5 47 0 0 3485 BE 6 41 6 0 1947 BE 6 50 9 0 3801 BE 6 43 6 0 2157 BE 6 53 4 0 4211 BE 1 15 9 0 0369 BLE 1 19 2 0 0653 BLE 2 18 3 0 0439 BLE 2 22 2 0 0777 BLE 2 19...

Page 11: ...0 4928 BE 4 63 2 0 6647 BE 4 56 7 0 5788 BE 4 67 4 0 7807 BE 5 62 5 0 6450 BE 5 74 5 0 8700 BE 5 66 0 0 7310 BE 5 78 7 0 9860 BE 6 71 8 0 7972 BE 6 85 8 1 0753 BE 6 75 4 0 8832 BE 6 90 0 1 1913 BE Smo...

Page 12: ...11 Installation examples Pozice 1 Damper hinge 2 Nut 3 Washer 4 Profile C 5 Washer C 6 Wall construction without fire resistance...

Page 13: ...63 68 68 67 65 62 48 57 65 70 70 69 67 64 50 w air velocity in the free cross section AxB i e before blades f frequency of octave band Sound power level corrected with filter A ps static pressure drop...

Page 14: ...67 65 62 48 w air velocity in the free cross section AxB i e before blades f frequency of octave band 13 21 26 26 25 23 20 6 21 29 34 34 33 31 28 14 28 36 41 41 40 38 35 21 34 42 47 47 46 44 41 27 38...

Page 15: ...re must be in the range from 5 C to 40 C and maximum relative humidity 80 Dampers must be protected against mechanic damages when transported and manipulated All effective safety standards and directi...

Page 16: ...case that dampers are found unable to serve for their function for any cause it must be clearly marked The operator is obliged to ensure that the damper is put into condition in which it is ready for...

Page 17: ...mechanism BLE24 BE24 12 54 with the communication and supply device BKNE 230 24 and actuating mechanism BLE24 BE24 12 ST 66 insulation inside of the blades I flanges with height 20 mm F WEIGHT kg Dob...

Page 18: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Reviews: