2
Smoke extraction dampers - single are shutters in smoke exhaust piping systems. Dampers are
designed to remove heat and combustion products (e.g. smoke) from single fire compartment.
In the event of fire the Smoke and Fire ventilation system opens the damper in the affected
section which removes combustion products and heat from this section.
The damper blade is operated by an actuating mechanism.
The dampers can be installed in various duct sizes with respect to the field of direct applications
according with EN 1366-9.
The field of direct applications based on tests results is acceptable according to EN 1363-1,
part A.1 and A.2, EN 1366-2, part 13 and EN 1366-10, part 9.
Smoke extraction dampers - single are classified as
The duct can be ended by KMM (TPM 002/96) grilles.
Damper characteristics
• CE certified acc. to EN 12101-8
• Tested in accordance with EN 1366-10
• Classified acc. to EN 13501- 4+A1
• External Casing leakage min. class B, Internal leakage min. class 3 acc. to EN 1751
• Cycling test in class C 10000 acc. to EN 12101-8
• ES Certificate No. 1391-CPR-2018/0106
• Declaration of Perfomance No. PM/SEDS-L/01/20/1
• Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19c
Summary of Contents for SEDS-L
Page 1: ......