28
Part Number: 000015431 Rev01 5/19
LOCATION OF CVD CONDENSING UNITS
The location selected for the CVD Condensing Unit must
meet the following criteria. If any of these criteria are not
met, select another location.
• The air temperature must be at least -20°F (-28.9°C)
but must not exceed 120°F (48.9°C).
• The location must not allow exhaust fan heat and/or
grease to enter the condenser.
• The location must not obstruct airflow through or
around the condensing unit. See below for clearance
requirements.
Minimum/Maximum Tcmpcraourcs
MNdcl
Minimum Air
Tcmpcraourc
Maximum Air
Tcmpcraourc
All Iic Maihinc
Hcad ScioiNns
35°F
2°C
110°F
43°C
QuicoQubc
CNndcnsing Unios
CVDF0600
CVDF0900
CVDT1200
CVDF2100
-20°F
-29°C
120°F
49°C
CVDF1400
CVDF1800
-20°F
-29°C
130°F
54°C