159
Refer to Sequence of
Operation &
Wiring Diagram
s
YES
YES
YES
NO
NO
NO
YES
NO
YES
Is harvest valve energized?
Is head pressure high
&
suction pressure low
in harvest?
Replace Harvest Valve
Is head pressure low
&
suction pressure low
in harvest?
Is head pressure normal
&
suction pressure normal
in harvest?
Refer to Harvest Pressure
Regulating Valve
Diagnostics
Repeat this flowchart
&
verify all data
Refer to Symptom #4
-
Will Not Harvest, Freeze
Cycle Normal & Ice Cubes ar
e
Melted Flowchart
Single Evaporator Systems with Dual Harvest V
alves: If one Harvest V
avle is open and the other is restricted / stuck closed you
may have
normal harvest pressures. Look for ice not melting on one side of the evaporator
.
Summary of Contents for Indigo ID0302A
Page 2: ......
Page 20: ...20 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 36: ...36 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 162: ...162 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 212: ...212 Part Number STH025 11 16 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 224: ...224 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 266: ...266 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 269: ...Part Number STH025 11 16 269 I0320 1PH AIR WATER Self Contained Air Water cooled ...
Page 270: ...270 Part Number STH025 11 16 I0500 1PH REMOTE Remote Air cooled 000007405_06 ...
Page 277: ...Part Number STH025 11 16 277 I1400 II1406 1800 1PH REMOTE Remote Condenser 000008864_04 ...
Page 278: ...278 Part Number STH025 11 16 I1400 I1406 I1800 3PH REMOTE Remote Condenser 000008864_04 ...
Page 288: ...288 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 289: ...Part Number STH025 11 16 289 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 290: ......
Page 291: ......
Page 292: ......
Page 293: ......
Page 294: ......
Page 295: ......