166
CONTROL BOARD RELAY TEST
The control board can be set to energize all relays for 3.5
minutes. This allows testing to verify control board relays
are closed and line voltage is available for ice machine
components - Water pump, dump valve, water inlet valve,
harvest valve(s), air compressor(s), contactor/compressor/
fan motor - The fan cycle control must close to energize
the fan motor.
1. Press power button to turn off ice machine.
2. Perform the following keystrokes on the display.
• Press Menu, scroll down to Service and press the right
arrow
• Scroll down to Diagnostics, press the right arrow and
select Diagnostics
• Display reads Control Board, press right arrow
• Scroll down to enbl relays and press right arrow to
start control board test
3. The control board will energize all relays and the
red light next to the relay. The red light indicates the
relay coil is energized.
4. Test for line voltage at the individual components.
A. Line voltage is present and the component is
non functional - Replace component
B. Voltage is not present at the component -
Proceed to step 5
5. Refer to wiring diagram and determine wire location
on the 9 pin molex connector for the component
you are testing.
6. Check for line voltage at the control board 9 pin
molex connector.
A. Line voltage at 9 pin connector - Repair wiring
to component
B. No power at 9 pin connector - Replace control
board
Summary of Contents for Indigo ID0302A
Page 2: ......
Page 20: ...20 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 36: ...36 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 162: ...162 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 212: ...212 Part Number STH025 11 16 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 224: ...224 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 266: ...266 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 269: ...Part Number STH025 11 16 269 I0320 1PH AIR WATER Self Contained Air Water cooled ...
Page 270: ...270 Part Number STH025 11 16 I0500 1PH REMOTE Remote Air cooled 000007405_06 ...
Page 277: ...Part Number STH025 11 16 277 I1400 II1406 1800 1PH REMOTE Remote Condenser 000008864_04 ...
Page 278: ...278 Part Number STH025 11 16 I1400 I1406 I1800 3PH REMOTE Remote Condenser 000008864_04 ...
Page 288: ...288 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 289: ...Part Number STH025 11 16 289 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 290: ......
Page 291: ......
Page 292: ......
Page 293: ......
Page 294: ......
Page 295: ......