PROGRAMMING A REPLACEMENT CONTROL BOARD
Indigo™ replacement control boards require the Model
number to be entered to activate the appropriate look up
tables for operation and diagnostic. This can be done two
different ways, USB Setup or Manual Setup.
USB Setup - Applicable when the control board is
operational and has a mechanical issue such as a sticking
relay. The asset data is transferred to the replacement
control board from the faulty control board. Refer to page
97 “Exporting Data To A Flash Drive” before installing the
replacement board.
Manual Setup - Applicable when the control board is
non-operational or data from the faulty board is suspect.
Install replacement control board and reapply power.
• G series (blue) control boards will go directly to the
Replacement Control Board screen and pause for
input - Select either “Manual” or “USB” setup option.
• E series (green) control boards require navigation to
the Replacement Control Board (Repl Cntl Bd) screen.
1. Press the Menu button.
2. Press the Down arrow until Service is highlighted,
then press the Checkmark.
3. Scroll down to Replacement Control Board and press
the Checkmark.
4. Select “Manual Setup” and press the Checkmark.
Verify the date correctly auto populates.
• Yes - Go to step 5
• No - Press the right arrow to activate the cursor, then
use up/down arrows to enter the correct date.
Summary of Contents for Indigo ID0302A
Page 2: ......
Page 20: ...20 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 36: ...36 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 162: ...162 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 212: ...212 Part Number STH025 11 16 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 224: ...224 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 266: ...266 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 269: ...Part Number STH025 11 16 269 I0320 1PH AIR WATER Self Contained Air Water cooled ...
Page 270: ...270 Part Number STH025 11 16 I0500 1PH REMOTE Remote Air cooled 000007405_06 ...
Page 277: ...Part Number STH025 11 16 277 I1400 II1406 1800 1PH REMOTE Remote Condenser 000008864_04 ...
Page 278: ...278 Part Number STH025 11 16 I1400 I1406 I1800 3PH REMOTE Remote Condenser 000008864_04 ...
Page 288: ...288 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 289: ...Part Number STH025 11 16 289 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 290: ......
Page 291: ......
Page 292: ......
Page 293: ......
Page 294: ......
Page 295: ......