COMPRESSOR ELECTRICAL DIAGNOSTICS
The compressor does not start or will trip repeatedly on
overload.
Check Resistance (Ohm) Values
NOTE: Compressor windings can have very low ohm
values. Use a properly calibrated meter.
Perform the resistance test after the compressor cools.
The compressor dome should be cool enough to touch
(below 120°F/49°C) to assure that the overload is closed
and the resistance readings will be accurate.
SINGLE PHASE COMPRESSORS
1. Disconnect power then remove the wires from the
compressor terminals.
2. The resistance values between C and S and between
C and R, when added together, should equal the
resistance value between S and R.
3. If the overload is open, there will be a resistance
reading between S and R, and open readings
between C and S and between C and R. Allow the
compressor to cool, then check the readings again.
THREE PHASE COMPRESSORS
1. Disconnect power and remove the wires from the
compressor terminals.
2. The resistance values between L1 and L2, between
L2 and L3, and between L3 and L1 should all be
equal.
3. If the overload is open, there will be open readings
between L1 and L2, between L2 and L3, and
between L3 and L1. Allow the compressor to cool,
then check the readings again.
Summary of Contents for Indigo ID0302A
Page 2: ......
Page 20: ...20 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 36: ...36 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 162: ...162 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 212: ...212 Part Number STH025 11 16 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 224: ...224 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 266: ...266 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 269: ...Part Number STH025 11 16 269 I0320 1PH AIR WATER Self Contained Air Water cooled ...
Page 270: ...270 Part Number STH025 11 16 I0500 1PH REMOTE Remote Air cooled 000007405_06 ...
Page 277: ...Part Number STH025 11 16 277 I1400 II1406 1800 1PH REMOTE Remote Condenser 000008864_04 ...
Page 278: ...278 Part Number STH025 11 16 I1400 I1406 I1800 3PH REMOTE Remote Condenser 000008864_04 ...
Page 288: ...288 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 289: ...Part Number STH025 11 16 289 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 290: ......
Page 291: ......
Page 292: ......
Page 293: ......
Page 294: ......
Page 295: ......