206
Self-Contained Recovery/Evacuation
1. Press the power button and cycle the ice machine
off.
2. Install manifold gauges, scale and recovery unit or
two-stage vacuum pump and open high and low
side on manifold gauges.
MANIFOLD SET
OPEN
VACUUM PUMP/
RECOVERY UNIT
CLOSED
OPEN
LOW SIDE
ACCESS
VALVE
HIGH SIDE
ACCESS
VALVE
OPEN
RECOVERY/EVACUATION CONNECTIONS
3. Perform recovery or evacuation:
A. Recovery: Operate the recovery unit as directed
by the manufacturer’s instructions.
B. Evacuation prior to recharging: Pull the system
down to 500 microns. Then, allow the pump
to run for an additional half hour. Turn off the
pump and perform a standing vacuum leak
check.
4. Follow the Charging Procedures.
Summary of Contents for Indigo ID0302A
Page 2: ......
Page 20: ...20 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 36: ...36 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 162: ...162 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 212: ...212 Part Number STH025 11 16 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 224: ...224 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 266: ...266 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 269: ...Part Number STH025 11 16 269 I0320 1PH AIR WATER Self Contained Air Water cooled ...
Page 270: ...270 Part Number STH025 11 16 I0500 1PH REMOTE Remote Air cooled 000007405_06 ...
Page 277: ...Part Number STH025 11 16 277 I1400 II1406 1800 1PH REMOTE Remote Condenser 000008864_04 ...
Page 278: ...278 Part Number STH025 11 16 I1400 I1406 I1800 3PH REMOTE Remote Condenser 000008864_04 ...
Page 288: ...288 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 289: ...Part Number STH025 11 16 289 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 290: ......
Page 291: ......
Page 292: ......
Page 293: ......
Page 294: ......
Page 295: ......