background image

 

 

WARNING

 

Line voltage is present inside control.  Contact 
with line voltage can cause serious injury or 
death. 

 

Differential, Anti-Short Cycle Delay, 
Temperature Offset, or Sensor Failure Operation 

To set or verify the Differential, Anti-Short Cycle 
Delay, Temperature Offset or Sensor Failure Operation 
use the following method: 

 

Factory  preset  temperature  control  code  settings,  as 
follows: 

A.

 

Press and hold MENU until the display 
changes to flashing SP.

 

B.

 

Press up and down (arrows) repeatedly until 
the desired function is displayed.

 

C.

 

Press MENU to display the function’s current 
value.

 

D.

 

Press up and down (arrows) until the desired 
value is displayed.

 

E.

 

Press MENU to save the new value. The 
display returns to the sensor temperature.

 

F.

 

If no setup entry is made for 30 seconds, the 
control reverts to the temperature display. 

 

Any saved control settings are non-volatile and remain 
in the control’s memory during power interruptions. 

 
Check Procedure

 

If the control system does not function properly, verify 
that the control is wired and set up properly. If the 
problem persists, use the following procedures to 
determine the cause of the problem 
 

IMPORTANT: 

Follow these troubleshooting procedures in the order 
presented. Do not skip any of the steps in the 
procedures. 
 
1.

 

Check for proper voltage to the control. 
A.

 

Remove the cover by loosening the four cover 
screws. 

B.

 

Use an AC voltmeter to check the voltage 
between the common and 120V or 240V 
terminals. 

C.

 

The voltage must be between  102 and 132 
volts for 120V applications; 177 and 264 volts 
for 208/230V applications. 

D.

 

If the voltage reading is not within the required 
range, check the power source and input power 
wires for problems. 

2.

 

Fault Codes 

If the LCD displays an alarm or fault code (SF or EE): 
 

Fault Code

 

Definition

 

Solution

 

SF flashing 

alternately with 

OP

 

Open temperature 

sensor or sensor wiring

 

See Step 3.  Cycle 

power to reset control.

 

SF flashing 

alternately with 

SH

 

Shorted temperature 

sensor or sensor wiring

 

See Step 3.  Cycle 

power to reset control

 

EE

 

Program failure

 

Reset the control by 

pressing MENU.   If 

problem persists, 

replace the control.

 

 

3.

 

Check for proper operation. 

 

IMPORTANT: 

Perform Steps 1 and 2 before performing these steps: 

A.

 

Disconnect the load from the output relay 
terminals. 

B.

 

Reconnect the sensor leads and supply power 
to the control. 

C.

 

Replace the cover. 

D.

 

Check the control settings for proper values. 

E.

 

Press and hold MENU until SP appears. 

F.

 

Press up and down (arrows) to change the set 
point temperature above and below the sensor 
temperature until the relay energizes and de-
energizes. 

G.

 

If the output relay does not perform as 
indicated, replace the control. 

H.

 

If proper operation of the control is verified, 
reconnect the load. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for K00364

Page 1: ...lock move the jumper from one pin to two pins P4 Jumper The P4 jumper labeled Jump 1 is used to set the control for heating or cooling mode Jump 2 is used to establish set point at either cut in or cut out Cubers Flake Nugget Chiplet Setting Control Set point Value To view and adjust set point follow these steps A Press MENU until the display flashes SP B Press MENU again to display the existing s...

Page 2: ...2110 South 26th Street P O Box 1720 Manitowoc WI 54221 1720 USA 8016563 Telephone 920 682 0161 Fax Sales 920 683 7589 Service Parts 920 683 7585 Other 920 683 7879 Sheet 1 of 4 Web Site www manitowocice com Rev 03 14 06 ...

Page 3: ...edures 1 Check for proper voltage to the control A Remove the cover by loosening the four cover screws B Use an AC voltmeter to check the voltage between the common and 120V or 240V terminals C The voltage must be between 102 and 132 volts for 120V applications 177 and 264 volts for 208 230V applications D If the voltage reading is not within the required range check the power source and input pow...

Page 4: ...8016563 Sheet 2 of 4 Rev 03 14 06 ...

Page 5: ...tubing IMPORTANT The thermostat must be wired to match the voltage of the ice machine The thermostat is pre wired for 115 volts Rewire thermostat if your ice machine is 240 volts 9 The control box line voltage wiring offers two options Connect thermostat L1 brown and L2 blue wires to contactor incoming line voltage side L1 and L2 OR Disconnect incoming power line wire nuts Remove quick connect fit...

Page 6: ...8016563 Sheet 3 of 4 Rev 03 14 06 ...

Page 7: ...Delay ASD 1 Temperature Offset OFS 0 Sensor Failure Operation SF 1 Cube 0 Flake Nugget Chiplet Keypad Locked Out Jumper Position Red Lead Sensor Probe Black Lead Sensor Probe Brown Lead Power Blue Lead Power Red 22AWG Lead Bin Switch or Toggle Switch White 22AWG Lead Bin Switch or Toggle Switch Route Sensor Wiring Here ...

Page 8: ...8016563 Sheet 4 of 4 Rev 03 14 06 ...

Reviews: