4. Harvest time is longer than normal and control
board indicates safety limit #2?
(Refer to Cycle Times/Refrigerant Pressures/24
Hour Ice Production Charts).
5. Discharge line temperature is greater than 160°F
at the end of the freeze cycle? (See Discharge
Line Temperature Analysis)
6. Connect refrigeration manifold gauge set to the
access valves on the front of the ice machine.
Establish baseline by recording suction and
discharge pressure and freeze & harvest cycle
times. (Refer to “
Freeze Cycle Refrigeration
System Operational Analysis Tables
” for data
collection detail).
7. Freeze cycle Head Pressure is in the range
indicated in the cycle time/24 hour ice production
and operational pressure chart?
If the head pressure is low refer to head pressure
control valve diagnostics.
8. Freeze cycle Suction Pressure normal?
Refer to analyzing suction pressure if suction
pressure is high or low.
9. Harvest cycle suction and discharge pressures
are lower than indicated in the cycle times/
refrigerant pressures/24 hour ice production
chart? Replace Harvest Pressure Regulating
solenoid.
Summary of Contents for MD0420A
Page 2: ......
Page 28: ...28 Part Number 040005626 5 17 This Page Intentionally Left Blank ...
Page 40: ...40 Part Number 040005626 5 17 This Page Intentionally Left Blank ...
Page 48: ...48 Part Number 040005626 5 17 This Page Intentionally Left Blank ...
Page 86: ...86 Part Number 040005626 5 17 This Page Intentionally Left Blank ...
Page 126: ...126 Part Number 040005626 5 17 This Page Intentionally Left Blank ...
Page 128: ...128 Part Number 040005626 5 17 M0420 M0500 M0700 M1000 1 PH SELF CONTAINED AIR WATER COOLED ...
Page 131: ......