Part Number STH042 3/14
103
Compressor Drawing Locked Rotor
The two likely causes of this are:
•
Defective starting component
•
Mechanically seized compressor
To determine which you have:
1. Install high and low side gauge.
2. Try to start the compressor.
3. Watch the pressures closely.
•
If the pressures do not move, the compressor
is seized. Replace the compressor.
•
If the pressures move, the compressor is
turning slowly and is not seized. Check the
capacitors and relay.
Compressor Drawing High Amps
The continuous amperage draw on start-up should not
be near the maximum fuse size indicated on the serial
tag.
The wiring must be correctly sized to minimize voltage
drop at compressor start-up. The voltage when the
compressor is trying to start must be within
±
10% of
the nameplate voltage.