Part Number STH042 3/14
105
High Pressure Cutout (HPCO) Control
Function
Stops the ice machine if subjected to excessive high-
side pressure.
The HPCO control is normally closed, and opens on a
rise in discharge pressure.
Specifications
Cut-out:
450 psig
±
10
Cut-in:
Automatic reset
(Must be below 300 psig to reset).
Check Procedure
1. switch to OFF.
2. Connect manifold gauge.
3. Hook voltmeter in parallel across the HPCO,
leaving wires attached.
4. On water-cooled models, close the water service
valve to the water condenser inlet. On self-
contained air-cooled models, disconnect the fan
motor.
5. Set to ON.
6. No water or air flowing through the condenser will
cause the HPCO control to open because of
excessive pressure. Watch the pressure gauge
and record the cut-out pressure.
Replace the HPCO control if it:
•
Will not reset (below 300 psig)
•
Does not open at the specified cut-out point
!
Warning
If discharge pressure exceeds 460 psig and the
HPCO control does not cut out, press the power
button to stop ice machine operation.
Summary of Contents for NEO
Page 2: ......
Page 20: ...20 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Page 30: ...30 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Page 46: ...46 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Page 94: ...94 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Page 107: ...Part Number STH042 3 14 107 This Page Intentionally Left Blank ...
Page 130: ...130 Part Number STH042 3 14 WIRING DIAGRAM ALL MODELS ...
Page 134: ...134 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Page 135: ......