CONTROL BOARD TIMERS
•
The ice machine is locked into the freeze cycle for
6 minutes before a harvest cycle can be initiated.
The freeze time lock in feature is bypassed on the
initial cycle (manual start or after a full bin/safety
limit condition).
If the Harvest float Switch is in the down position
for 10 continuous seconds during the start of a
freeze cycle, a harvest sequence is initiated.
•
The maximum freeze time is 60 minutes at which
time the control board automatically initiates a
harvest sequence.
•
The maximum harvest time is 3.5 minutes. The
control board automatically initiates a freeze
sequence when these times are exceeded.
•
The water fill valve is de-energized 1 minute after
the freeze cycle starts. The control board will
energize the water inlet valve one more time 3
minutes into the freeze cycle.