80
Part Number STH042 3/14
Suction Pressure Low Checklist
Improper Installation
•
Refer to “Installation/Visual Inspection Checklist”
on page 64.
Discharge Pressure
•
Discharge pressure is too low, and is affecting
suction pressure, refer to “Freeze Cycle Discharge
Pressure Low Checklist”
Improper Refrigerant Charge
•
Undercharged
•
Wrong type of refrigerant
Other
•
Non-Manitowoc components in system
•
Improper water supply over evaporator refer to
“Water System Checklist” on page 65.
•
Loss of heat transfer from tubing on back side of
evaporator
•
Restricted/plugged liquid line drier
•
Restricted/plugged tubing in suction side of
refrigeration system
•
TXV starving
NOTE: Do not limit your diagnosis to only the items
listed in the checklists.
Summary of Contents for NEO
Page 2: ......
Page 20: ...20 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Page 30: ...30 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Page 46: ...46 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Page 94: ...94 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Page 107: ...Part Number STH042 3 14 107 This Page Intentionally Left Blank ...
Page 130: ...130 Part Number STH042 3 14 WIRING DIAGRAM ALL MODELS ...
Page 134: ...134 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Page 135: ......