37
RNF1020C/RFF1220C/RNF2000C/RFF2200C
Remote Air-cooled Condensing Unit Models
When the toggle switch is placed in the ON position the
following controls must be in the closed position before
the ice machine will start:
A. Bin Thermostat
B. High Pressure Cut-out Switch
C. Ice Chute Safety Switch
D. Low Pressure Switch
E. Low Water Level Switch
Placing the toggle switch in the ON position starts the gear
motor. After 8 minutes of correct rotation the time delay
ends and the liquid line solenoid valve opens.
• When the refrigerant pressure is high enough to close
the low-pressure control the contactor coil energizes
and the compressor and condenser fan motor starts.
The ice machine will continue to make ice until ice contacts
the bin thermostat and the liquid line solenoid valve closes
and the refrigeration system pumps down.
• The refrigerant pressure drops and the fan cycling
pressure control opens stopping the.
• When the refrigerant pressure is low enough to open
the low pressure control, the contactor coil is de-
energized and the compressor and condenser fan
motor stop.
The ice machine remains off until ice no longer contacts
the bin thermostat.
Summary of Contents for RFF
Page 2: ......
Page 34: ...THIS PAGE INTENTIONALLY LEFT BLANK 34 Part Number 000015433_03 5 20 ...
Page 146: ...THIS PAGE INTENTIONALLY LEFT BLANK 146 Part Number 000015433_03 5 20 ...
Page 160: ...THIS PAGE INTENTIONALLY LEFT BLANK 160 Part Number 000015433_03 5 20 ...
Page 161: ......
Page 162: ......
Page 163: ......