Maintenance
Section 4
4-12
Part Number 80-1561-3
Removal from Service/Winterization
GENERAL
Special precautions must be taken if the ice machine is
to be removed from service for an extended period of
time or exposed to ambient temperatures of 32°F (0°C)
or below.
Follow the applicable procedure below.
SELF-CONTAINED WATER-COOLED ICE MACHINES
1. Disconnect the electric power at the circuit breaker
or the electric service switch.
2. Turn off the water supply.
3. Remove the water from the water trough.
4. Disconnect and drain the incoming ice-making water
line at the rear of the ice machine.
5. Blow compressed air in both the incoming water and
the drain openings in the rear of the ice machine
until no more water comes out of the inlet water lines
or the drain.
6. Make sure water is not trapped in any of the water
lines, drain lines, distribution tubes, etc.
7. Disconnect the incoming water and drain lines from
the water-cooled condenser.
8. Insert a large screwdriver between the bottom spring
coils of the water regulating valve. Pry upward to
open the valve.
9. Hold the valve open and blow compressed air
through the condenser until no water remains.
Pry Open the Water Regulating Valve
AUCS
®
Accessory
Refer to the AuCS
®
Accessory manual for winterization
of the AuCS
®
Accessory.
!
Caution
If water is allowed to remain in the ice machine in
freezing temperatures, severe damage to some
components could result. Damage of this nature is
not covered by the warranty.
SV1624