132
Part N
umber 80-
1479-
3 7/10
Refer to Symptom #2
Freeze Cycle Operational
Analysis Table
Refer to Heavily Scaled
Cleaning Procedure
Discharge line temperature is normal
at the end of the freeze cycle?
S850/S1000 (A/W) = >140F/60C
All other S Models = >150F/65C
Refer to Manual
Cleaning Procedure
Is the evaporator dirty?
(Dry evaporator first then check)
YES
YES
NO
NO
NO