4
3.
Quantity of AFD required = (75 m³ x 12) / (800 m
3
/h) = 900/800 = 1.2 units
4.
1.2 units → 2 units required
.
ELECTRICAL REQUIREMENTS
1.
The units require a minimum of 110 or 220 volts AC, 60 Hz to operate properly; however, maximum air flow
performance requires 110 or 220 volts AC, 60 Hz. (unique voltage requested on purchase).
2.
Due to momentary start-up current surge, the unit requires a 15 amp circuit that is free of other loads.
3.
Extension cords used for this unit must be listed, heavy duty industrial grade 3-wire type and be equipped with
hospital grade plugs (if used in a health care facility). Use of larger numerical gauge (lower capacity wire) power
cord(s) may result in electrical shock, fire hazards and/or damage to unit. The cord(s) must be in good condition
and in continuous lengths (no splicing) and should not exceed a total of 5 m., in length. Make sure that any
extension cords used do not reduce power to the unit to less than 110 or 220 volts. Use of a voltmeter to
confirm adequate voltage is recommended.
4.
Check to ensure that any circuit to which the unit is connected is protected by a 15 amp circuit breaker. The unit
itself is equipped with a 5 amp circuit breaker.
5.
The units should be connected to a three-prong, properly grounded electrical outlet.
6.
To avoid personal injury, fire
hazards and/or damage to the unit’s electrical system and power cord, do not
connect or disconnect the power cord to an electrical outlet unless the unit is switched to the “OFF” position
.
KEY COMPONENTS
Models of TRI-KLEEN 500UV BR series - side view showing internal components
Air Exhaust (on top of unit, but
undeneath Sound Baffle)
Sound Baffle
Control panel
Pre-Filter Access Door (hinged
dor lifts up to provide access
to pre-filter)
Motorized Impeller
Air Inlet Grille
Pre-filter
Swivel Casters
Only models HC500FUV
Ultraviolet Germicidal Lamp
(UV Lamp)
Cord Wrap
HEPA Cylindrical Filter
HEPA Filter Retaining Bracket
Access door - remove screwed
door for accessing for the
maintenance of HEPA Filter
and UV lamps.
Summary of Contents for TRI-KLEEN 500 UV BR