6. Parameter Input
• DOK-CONTRL-DDC+MDD+DLC-ANW1-EN-E1,44 • 01.97
41
6.3.
Parameter Input Preparations
Applying distribution
voltage
The distribution voltage must be applied to the drive controller for inputting
parameters.
3 x 230 V AC (+ 10 % - 15%) (with the DDC 1.1)
Conditions at the
Mains
Before applying the distribution voltage check whether the mains meets the
requirements of the drive controller. Guidelines for earthing conditions of the
supply source, mains connections, control circuits, E-stop circuits and so on
are detailed in the Project Planning Manual DDC (209-0069-4381-XX).
Drive Components
The drive components installed must be suited to the respective mains
voltage.
Wiring
Check wiring for short-circuits, breaks, incorrect connections and lead dia-
meters.
Earthing
• Make sure that the earthing corresponds to all the INDRAMAT connection
recommendations.
• Include the applicable protective measures required for the machine.
• Earth the motor to the drive controller.
• Connect the earth conductor of the drive controller to the mains earth.
Danger
Electromagnetic
compatibility
• Connect the housing of the drive controller with the machine chassis so
that it is electrically conductive.
Power leads
• The leads of the drive controllers to the motor should be twisted or a four-
strand cable (3x phase, 1x earth).
• Check to make sure that the lead diameters comply with the EN 60204
guidelines.
• The required lead diameters are detailed in the motor documentation.
Contact points and
plug-in connectors
Check for:
• secure contacts - they may not be dirty or moist
• contact points must be firmly and permanently in place
• subminiature connectors must be firmly and permanently in place
Please ascertain that the data on the configuration rating plate
agrees with that on the plug-in module inserted into the drive con-
troller. If these do not agree, then damage to the AC servo drive and
the mechanics of the machine can result!
Source of danger:
Risk of accident from dangerous voltage levels
Possible consequences:
Danger to life and limb.
How to avoid:
Do not undo the earth connections. They create a
functional earth with protective functions.