6. Parameter Input
• DOK-CONTRL-DDC+MDD+DLC-ANW1-EN-E1,44 • 01.97
44
6.5.
Explanatory Notes on Several Important DLC
Parameters
DLC parameters important to the setup mode are explained in detail in the
following section.
The programming guidelines "DLC1-A Single-Axis Programming Modules
for Digital Drive Control" explain all DLC parameters in detail (see doc. no.
109-0852-4102-XX).
Maximum Speed
Parameter A1 0 0
Input range: 0.10 ... 50 000.00
Decimal places: 2 or 3 depending on parameter B 007
The following value results for Example 1, acc. to section 6.6:
Input value: 000300,00
Setup speed
Parameter A 1 0 1
Input range 0.10 ... 50 000.00
Decimal places: 2 or 3 depending on parameter B 007
Speed in setup mode if system operation jogging forward or backward is set
to logical 1.
A 101
≤
A 100
Caution
Acceleration
Parameter A 1 0 2
Input range: 1 ... 9999 9999
Decimal places: 0 or 1 depending on parameter B 007
Check whether the acceleration programmed here is acceptable to the
mechanical system of the machine.
Value for example 1, section 6.6
a = 1m/S
2
v
max
n
max
60
------------
VK
•
=
v
max
= maximum speed
n
max
= maximum motor rpm
VK = feed constant
v
max
n
max
60
-----------
h
•
=
Z
1
Z
2
-------
2880min
-1
60
---------------------------
=
•
10mm
35
56
------
•
•
300
mm
s
----------
=
The speed which may be used in setup mode depends on the con-
struction of the machine. To avoid damage to the machine, do not
select a very high speed.