6. Parameter Input
• DOK-CONTRL-DDC+MDD+DLC-ANW1-EN-E1,44 • 01.97
48
Display and language
selection
Parameter B 0 0 7
The language and the number of decimal places of the CTA are fixed here.
Encoder input and
working direction of the
external position
measuring device
Parameter B 0 1 6
External position
measurement
resolution
Parameter B 0 1 7
0 0 0 0 1 2 5 0
Input range: 100 ... 20000
Number of pulses per encoder revolution or linear scale number of pulses
per motor revolution.
Example of linear scale: division period = 20
µ
; feed constant = 5mm; pulse
replication = 5-fold
Input value: 000 01250
Feed constant for
external position
measurement
Parameter B 0 1 8
Input range: 0.1 ... 5000.0000
Decimal places: 4 or 5 depending on parameter B 007
Path per revolution of the external position encoder or with linear scale - tra-
versing path for the number of pulses as per B 017.
Example: feed constant 5 mm
Input value: 0005.0000
0 0 0 2 0 0 0 0
02 = standard
03 = additional decimal places for an even finer resolution
00 = German; 01 = English; 02 =French;
03 = Spanish; 04 = Italian; 05 = Portugese
1 0 0 0 0 0 0 0
Working direction:
0 = drive motor and external position encoder have same
rotational direction
1 = drive motor and external position encoder do not have
same rotational direction
Encoder input:
1 = DEF 1 plug-in module
2 = DEF 2 plug-in module
3 = DFF plug-in module
B017
feed constant
division period
--------------------------------------
pulse replication
5mm
0.02mm
---------------------
5
•
=
•
1250
=
=