6. Parameter Input
• DOK-CONTRL-DDC+MDD+DLC-ANW1-EN-E1,44 • 01.97
53
6.8.
Example 3 - Linear Axis with Direct Position
Measurement
Fig 6.10: Linear axis with direct position measurement capabilities
Parameter for setup
mode
The parameters needed for setup mode are listed below. All other parame-
ters must be set to 00000000. There is a list of all parameters at the end of
this section. Details on important parameters can be found in section 6.5.
Warning
Drive controller
Start reference
~
DSF
Z
2
= 58
Z
1
= 29
1200
h = 10 mm/rev.
v
max
= 14.4 m/min
a
max
= 1 m/s
2
n
max
= 2880 min
-1
FPdirmes
E02
E01
spacing 20
µ
Linear scale
5-fold digital.
electronics
slide
Source of danger:
Incorrect parameters input.
Possible consequences:
Possible damage to machine.
How to avoid:
Only personnel with machine expertise may input
parameters.
• Check parameters with *. The values listed in the
following parameter list only apply to Example 3.
These must be adjusted to the machine.
• The speed control parameters marked with **
depend on the motor-controller combination,
load and the machine mechanics. Set standard
speed control parameters.
• Parameter overload factor marked with *** must
be matched to the motor/controller combination.
See setting overload factor.
• The machine manufacturer is responsible for the
DLC parameters. These can only be changed
with his permission.