background image

Installation Guidelines

 

11/18

page 6 of 7

For more information, contact your local Mannington representative or visit manningtoncommercial.com

Crafted with purpose

3.  

Amtico RP18:

 A solvent-free 1-component silane polymer-base adhesive. Moisture limits per ASTM F-1869 of 10 lbs. 

maximum MVER and/or 95% relative humidity per ASTM F-2170 and a pH limit of 12. Amtico RP18 works well over 
porous subfloors using a 1/16” x 1/32” x 1/32” U-notch trowel with an approximate spread rate of 250 sq. ft. per gallon 
and non-porous subfloors using a 1/16” x 1/32” x 5/64” U-notch trowel with an approximate spread rate of 350 sq. ft. 
per gallon. It is recommended for use in all areas subject to some heat and moisture variations, like what may be 
found adjacent to sunny windows and bathrooms. Amtico RP18 must be used for installing LVF in wet areas such as 
locker rooms and should also be used for areas with high point loads and direct sun exposure. See adhesive spec and 
label for details.

4.  

XpressStep Spray Adhesive:

 Water based spray adhesive recommended for the installation of Mannington 

Commercial LVF over porous and non-porous subfloors. Moisture limits are 10 lbs. maximum MVER or 95 % relative 
humidity with a pH maximum limit of 11. Spread rate approximately 150-185 sq. ft. per can. 

XpressStep Premium Spray Adhesive:

 Moisture limits are 10 lbs. MVER or 98% relative humidity with a pH maximum 

limit of 12. Spread rate approximately 150-185 sq. ft. per can. 

XpressStep Spray Adhesives

 may be used under hospital beds, operating room tables and heavy rolling loads.

Mannington Commercial will not assume responsibility for floor covering failure due to hydrostatic pressure or moisture 
vapor emission. The final responsibility for determining if the concrete is dry enough for installation of the flooring 
lies with the floor covering installer. The adhesives are designed to be moisture resistant to accommodate the water 
of hydration contained in new slabs or initial mixing; they are not to be considered remedial solutions to concrete 
subfloors with a history of moisture problems.

Important:

 Temperature directly affects adhesive working and setting times. Warmer temperatures shorten working 

times and colder temperatures lengthen working times of adhesive. Follow instructions on container for proper 
application.

Installation

Adhesive application: Follow the instructions on the adhesive labels.

1.   Use a trowel with appropriate notch size. Do not use worn trowels (approximately 600 sq. ft. usage on concrete).
2.    Spread adhesive evenly with proper trowel held at 60 degree angle, avoiding skips or voids and excessive adhesive 

application.

3.  Only spread sufficient adhesive that can be covered within the adhesive working time.
4.  Tiles/planks must be placed into adhesive as specified (follow label directions).
5.  Install rows to chalk line making sure tiles/planks are precisely aligned with chalk line and adjacent tiles.
6.  Randomly check tiles/planks for complete coverage of adhesive onto back of tile, especially near the end of each 

adhesive spread. If there is little or no adhesive transfer, or if the adhesive has flashed off or skinned over, adequate 
bonding may not be possible. Scrape the flashed-off adhesive from the floor, and spread fresh adhesive.

7.   If tiles/planks shift, use releasable masking tape diagonally over seams to keep tiles tight and aligned.
8.  Wet-set application: Do not work on top of freshly installed flooring. This will minimize tile/plank shifting and adhesive 

displacement, and prevent wet adhesive from oozing up and getting onto the surface of the new flooring.

9.  The floor must be rolled in both directions using a 100-lb. 3-section roller. Roll floor as soon as conditions permit, 

without the tiles/planks sliding or adhesive bleeding to the surface. Roll floor again, 90 degrees to the first direction, 
within 1 hour. Adhesives should provide 100% uniform adhesive transfer (no visible trowel ridges) onto the back of the 
tile/plank, and not cause adhesive to squeeze out between tiles/planks. Pressure Sensitive Adhesive will not transfer 
100% to the backing of the tile/plank. Be sure not to exceed the 3 hour working time.

10.  Clean excess adhesive as you install, before it is allowed to dry. Use a soapy, clean, soft cloth to remove wet excess 

adhesive.

Summary of Contents for Amtico

Page 1: ...Cutback adhesive as Bleed Through may occur Mannington LVF is not suitable for external installation or unheated locations Mannington flooring adhesive job site and subfloor must be acclimated to a st...

Page 2: ...of water directly onto the concrete subfloor If the water droplet does not dissipate within 60 to 90 seconds the subfloor is considered non porous Concrete subfloors must have a minimum compressive s...

Page 3: ...ilient Floor Covering Institute RFCI document Recommended Work Practices for Removal of Existing Resilient Floor Coverings for guidance www RFCI com 5 Perform corrective actions necessary for elevated...

Page 4: ...manent HVAC source is utilized it must provide proper control of both temperature and humidity to recommended or specific levels for the appropriate time duration 2 Flooring materials Check that the q...

Page 5: ...t each tile for visual defects before installing Installation of the flooring implies acceptance of materials Adhesives Mannington adhesives are specifically formulated to be fully compatible with bac...

Page 6: ...rs with a history of moisture problems Important Temperature directly affects adhesive working and setting times Warmer temperatures shorten working times and colder temperatures lengthen working time...

Page 7: ...sure for long periods of time should utilize window treatments and or utilize Amtico RP18 Adhesive in these areas 3 Protecting new installations New installations must be protected while the adhesive...

Reviews: