32
D00619EN
-
v0
SWING OPERATOR
-
INSTALLATION MANUAL
CARACTERÍSTICAS MECÁNICAS
6.2 Management and Use
6.2.1 Operational Logic Settings
LOGIC
SETTING
DESCRIPTION
LOW
-
ENERGY
In all operating modes (excluding Stop Closed) a motorised reduced
-
speed
opening (velocity Low Energy) and an augmented stop period (disabled per-
sons stop time) can be achieved using the disabled persons opening con-
trols (in the configuration input [AUX IN 1 configuring the parameter 15=0,
section ‘Management of the Operational Parameters
-
display’]). Closing will
be carried out by the spring with obstacle control.
PUSH & GO:
Manually moving the stationary leaf when in the closed position will automatically cre-
ate an opening and closing manoeuvre. To configure this logic setting it is necessary
to set DIP 3 = ON.
SAFE CLOSE
If the safety sensor mounted on the closing leaf and which is connected to the elec-
tronic card (in Safe Close mode) detects an obstacle during the closing phase, it inter-
rupts and quickly reverses the direction of movement of the leaf, opening it completely
at the standard speed and closing it again normally.
If the detection takes place during the opening phase, the system does not react and
the door continues along its course.
SAFE OPEN
If the safety sensor mounted on the closing leaf and which is connected to the elec-
tronic card (in Safe Open mode) detects an obstacle during the opening phase, it in-
terrupts the movement of the leaf; if later it detects nothing, the leaf returns to its
opening movement and then closes at normal speed.
If the detection takes place during the closing phase. the system does not react and
the door continues along its course.
Where the leaf is installed close to a wall (for example in a corridor) a value (% of the
total course) should be introduced so that the sensor detects the wall as an obstacle.
This value can be modified using the parameters 20 (see section ‘Management of the
Operational Parameters
-
display’) or through the
MillenniumWare
software.
Operational
Logic Settings
Manual
With this logic setting the controls connected to START1 and START2 are disabled,
allowing manual opening and closing. The opening and closing safety sensors are
active only in the case when motorised opening is required for disabled persons.
1 radar
EXIT RADAR ONLY: Only controls the START2 input on the electronic control card.
A signal sent from the sensor connected to this input causes the opening and subse-
quent closing of the leaf. Locking the door with a lock or motor (in cases where a lock
has not been chosen) in the closed position, depends on the type of lock used and
the configuration of parameter 14.
2 radars
ENTRY AND EXIT RADAR: Both inputs START1 and START2 on the electronic con-
trol card are enabled. A signal sent from a connected sensor to one of the inputs
causes the opening and subsequent closing of the leaf. Locking the door with a lock
or motor (in cases where a lock has not been chosen) in the closed position, depends
on the type of lock used and the configuration of parameter 14.
Stop
closed
The door is locked in the closed position. The device controls the complete closing of
the leaf. In this logic setting the inputs START1 and START2 on the electronic control
card cannot be controlled and, where present, the electronic lock locks the leaf.
If there is no electronic lock, the leaf is locked by the motor.
Stop
open
The door is locked in the open position. The device controls the complete opening of
the leaf. In this logic setting the inputs START1 and START2 on the electronic control
card cannot be controlled.
Anti
-
crushing during opening
During the opening phase, the leaf encounters an obstacle preventing movement.
The operator interrupts the movement of the leaf for a few seconds and slowly closes
it completely. The sensitivity value can be regulated using parameter 06 (see section
‘Management of the Operational Parameters
-
display’) or through the MillenniumWare
software.
Anti
-
crushing during closing
During the closing phase, the leaf encounters an obstacle preventing movement.
The operator immediately inverts the leaf movement and opens it completely.
The subsequent closing is performed slowly. The sensitivity value can be regulated
using parameter 06 (see section ‘Management of the Operational Parameters
-
display’) or through the MillenniumWare software.
Summary of Contents for VECTOR
Page 1: ...Installation Manual VECTOR Operator ...
Page 15: ...14 D00619EN v0 SWING OPERATOR INSTALLATION MANUAL 5 4 A 5 4 B Fig 4 Fig 5 D A B E C F ...
Page 16: ...15 D00619EN v0 SWING OPERATOR INSTALLATION MANUAL 5 4 C 5 4 D Fig 6 Fig 7 A A A A ...
Page 19: ...18 D00619EN v0 SWING OPERATOR INSTALLATION MANUAL 5 5 A 5 5 B Fig 12 Fig 13 A A ...
Page 47: ...46 D00619EN v0 SWING OPERATOR INSTALLATION MANUAL CARACTERÍSTICAS MECÁNICAS 10 4 Notes ...