background image

.

                          Maple Systems Inc., 808 134th Street SW, Suite 120, Everett, WA 98204-7333                                
1036-0203                           

     Page 3 of 4                               

        Rev. 01, 10/11/2015 

EZware Settings 

The following table lists the communications settings that must be configured in 
EZware. These settings can be found in the 

Edit-System Parameters

 menu under the 

Device

 

Properties

 tab. Please note: 

 

The 

Recommended Settings 

column provides the recommended setting 

based upon the default settings most commonly used in Siemens modules.

 

 

The 

Options 

column lists EZware’s options; your PLC may not support 

every option 

 

Name

 

Recommended

 

Settings

 

Options

 

Important Notes

 

Name: 

Siemens S7-200 
Smart (PPI) 

 

Description label 

HMI or PLC 

PLC 

 

 

Location 

Local 

Local, Remote 

Select 

Local

 if PLC directly 

connected to HMI,

 Remote 

if PLC connected thru 
another HMI. 

PLC type: 

Siemens S7-200 
Smart (PPI) 

 

 

PLC I/F: 

RS485 2W 

RS-232,  
RS-485 2W, 
RS-485 4W 

Must match the controller port 
setting. 

PLC default station 
no.: 

1-126 

Must match the node address 
assigned to the PLC. 

Setting: COM: 

COM1 

COM1-COM3 

Serial port of the HMI connected 
to the controller. 

Settings: Baud rate 

9600 

9600, 19200, 
187.5K 

Must match the PPI port 
setting.  Use the fastest 
baud rate supported by the 
controller. 

Settings: Data Bits 

7 or 8 

Must match the PPI port setting. 

Settings: Stop Bits 

1 or 2 

Must match the PPI port setting. 

Settings: Parity: 

Even 

Even, Odd, 
None 

Must match the PPI port setting. 

Summary of Contents for Graphic HMIs

Page 1: ... Please refer to the Installation and Operations Manual for information on connecting multiple Graphic HMIs to a single PLC port Communications Cable The Graphic HMI should be connected to the controller s PPI port A list of communications cables offered by Maple Systems as well as cable assembly instructions to assist you in assembling your own communications cable are available on our website at...

Page 2: ...ddddd V Memory SMW 0 1534 dddd Special Memory T 0 255 ddd Timer C 0 255 ddd Counter AIW 0 110 ddd Analog Input AQW 0 110 ddd Analog Output VD 0 20476 ddddd V Memory Double Word Discrete Memory The following table lists the PLC s discrete memory ranges that the Graphic HMIs are able to access Please note that your PLC s memory range may be smaller or larger than that supported by these HMIs The fol...

Page 3: ...tant Notes Name Siemens S7 200 Smart PPI Description label HMIor PLC PLC Location Local Local Remote Select Local if PLC directly connected to HMI Remote if PLC connected thru another HMI PLC type Siemens S7 200 Smart PPI PLC I F RS485 2W RS 232 RS 485 2W RS 485 4W Must match the controller port setting PLC default station no 2 1 126 Must match the node address assigned to the PLC Setting COM COM1...

Page 4: ... sec 1 0 0 1 to 25 5 Adjust if longer timeout is required Settings Turn around delay ms 5 0 1000 Timeout period between HMI polls Settings Send Ack Delay 30 Settings Reserved 1 0 Not Applicable Settings Reserved 2 0 Not Applicable Settings Reserved 3 0 Not Applicable Interval of block pack words 5 0 512 Max read command size words 16 Not Adjustable Max write command size words 2 Not Adjustable ...

Reviews: