HMC3-M1212P0200
38
HMC3000 Series I/O Module Guide
38
Reference the table below when configuring the PWM Configuration Registers:
Output Mode
Register Value
Normal PWM (fixed frequency)
1
Normal PWM (variable frequency)
2
CW/CCW (fixed frequency)
3
CW/CCW (variable frequency)
4
Pulse/Direction (fixed frequency)
7
Pulse/Direction (variable frequency)
8
Trapezoidal (Fixed Pulse Mode)
9
Reference the table below when configuring each Analog Input Configuration Register (MWnn60-MWnn61):
Input Signal Type
Register Value
Voltage, 0 to 10V
1
Voltage, 0 to 5V
6
Current, 4 to 20mA
2
Current, 0 to 20mA
3
The values in the appropriate analog input register range from 0-64000, with over and under indications at
65000 and 65001.
Expansion Module
Reg Value
Input Values
0 to 20mA
4 to 20mA
0 to 10V
0 to 5V
0
0mA
4mA
0V
0V
16000
5mA
8mA
2.5V
1.25V
32000
10mA
12mA
5V
2.5V
48000
15mA
16mA
7.5V
3.75V
64000
20mA
20mA
10V
5V
65000
< 0mA
< 4mA
< 0V
< 0V
65001
> 20mA
> 20mA
> 10V
> 5V
Summary of Contents for HMC3-M0808P0401T
Page 26: ...HMC3 M0808P0401T 26 HMC3000 Series I O Module Guide 26...
Page 34: ...HMC3 M0808Y0401T 34 HMC3000 Series I O Module Guide 34...
Page 41: ...HMC3 M1212P0200 41 HMC3000 Series I O Module Guide 41 HSC Quadrature...
Page 48: ...HMC3 M1212Y0200 48 HMC3000 Series I O Module Guide 48 HSC Quadrature...
Page 56: ...HMC3 M1210P0201 56 HMC3000 Series I O Module Guide 56...
Page 67: ...HMC3 M1614Y 67 HMC3000 Series I O Module Guide 67 HSC Single Phase Down Counter HSC Quadrature...
Page 71: ...HMC3 M1616P 71 HMC3000 Series I O Module Guide 71 HSC Single Phase Down Counter HSC Quadrature...
Page 72: ...HMC3 M1616P 72 HMC3000 Series I O Module Guide 72...