I/O Expansion Module Overview 

 

HMC3000 Series I/O Module Guide 

 

8.

 

For the Analog configuration of this module, the behavior is the same; choose the channel and the 
configuration, then click the 

Confirm

 button to complete the configuration. 

 

9.

 

Options for the Analog configuration of this specific module: 

 

 

 

Summary of Contents for HMC3-M0808P0401T

Page 1: ...ource _____________________ www maplesystems com Maple Systems Inc 808 134th St SW Suite 120 Everett WA 98204 425 745 3229 I O Module Guide For the HMC3000 Series For use with the following HMC3000 Se...

Page 2: ...ple Systems equipment is prohibited without the specific written permission of Maple Systems WARRANTY Warranty Statements are included with each unit at the time of purchase and are available at www m...

Page 3: ...finitions 10 Configuring High speed Counters 12 Configuring Pulse Width Modulation PWM Outputs 14 HMC3 M0808P0401T 19 Specifications 19 Configuration 21 Wiring 23 HMC3 M0808Y0401T 27 Specifications 27...

Page 4: ...ction 4 HMC3000 Series I O Module Guide 4 Specifications 57 Configuration 59 Wiring 61 HMC3 M1614Y 64 Specifications 64 Configuration 65 Wiring 66 HMC3 M1616P 68 Specifications 68 Configuration 69 Wir...

Page 5: ...age 0 5V 0 10V Current 0 20mA 4 20mA HMC3 M1212P0200 12 Digital Inputs 2 high speed pairs up to 200kHz 12 Digital Outputs 2 PWM up to 1kHz 2 Analog Inputs Voltage 0 5V 0 10V Current 0 20mA 4 20mA HMC3...

Page 6: ...les The expansion modules for the HMC3000 base units attach onto the back of the HMC3000 via expansion slots and are secured with a Phillips screw on the top right and bottom left corners of the modul...

Page 7: ...ose the IO Allocation window or click the Configure button to pre configure the module s input and output channels 5 In this example Slot 1 is identified with an I O module along with a description an...

Page 8: ...from a window or via a power up task The available options will depend on the module being configured Select the channel and desired configuration then click the Confirm button to save the configurati...

Page 9: ...Module Guide 9 8 For the Analog configuration of this module the behavior is the same choose the channel and the configuration then click the Confirm button to complete the configuration 9 Options fo...

Page 10: ...s Each analog input terminal is associated with an internal Input Register XW in the tag database of the HMC3000 Similarly each analog output terminal is associated with an Output Register YW Sinking...

Page 11: ...act can handle up to 230VAC with a 2A load per contact For DC loads each relay output contact can handle a 2A load per contact for up to 30VDC Analog Voltage Analog voltage inputs can measure DC volta...

Page 12: ...riggers the count The counter will increment by one on each bit transition The counter can operate on a falling default or rising edge Enable Bit The counter will not run unless this bit is set If thi...

Page 13: ...Up Counter HSC 011 Quadrature To Implement High speed Counter Operation 1 Connect a device that will provide the high speed pulses to one of the high speed inputs on the expansion module 2 Configure...

Page 14: ...r LSW MSW MW0303 MW0304 MW0309 MW0310 Configuring Pulse Width Modulation PWM Outputs Maple Systems HMC3000 I O modules have built in Pulse Width Modulation functionality Specific registers and bits ar...

Page 15: ...n Register MWnn24 MWnn30 Value 1 for this mode Frequency Setting Register MWnn25 MWnn31 Range 1 to 200000 ON Duty Setting Register Duty Cycle MWnn27 MWnn33 Range 0 to 100 Pulse Enable Flag Mnn576 Mnn5...

Page 16: ...sed The frequency can be adjusted while running place a 4 in the Config register instead of 3 and the Duty Cycle is fixed at 50 Function Register Description Output PWM Pulse Y0 Channel 1 Y1 Channel 2...

Page 17: ...can be adjusted while running place an 8 in the configuration register and the Duty Cycle is fixed at 50 Function Register Description Output PWM Pulse Y0 Channel 1 Y1 Channel 2 Physical Output Confi...

Page 18: ...mode Minimum Frequency Register MWnn25 MWnn31 Range 1 to 100000 Maximum Frequency Register MWnn27 MWnn33 Range 1 to 100000 Acceleration Time Register MWnn37 MWnn38 Range 0 to 65535 Deceleration Time...

Page 19: ...which are high speed inputs It also has eight digital sourcing PNP outputs two of which can be configured for PWM operation This module also has 4 universal analog inputs Voltage Current Thermocouple...

Page 20: ...Output Voltage 22 VDC Maximum ON Output Voltage 30 VDC Minimum OFF Output Voltage 0 2 VDC Maximum OFF Output Voltage 1 VDC Rated Load 250mA 24VDC Nominal load 96 6W resistive 24VDC 6VA inductive UPF...

Page 21: ...ite HSC Reset Bit Mnn081 Mnn177 Read Write Output Flag Y2 Y3 PWM Outputs Channel 1 Channel 2 Output Y0 Y1 Read Only PWM Configuration Register MWnn24 MWnn30 Read Write Frequency Setting Register MWnn2...

Page 22: ...Pulse Direction variable frequency 8 Trapezoidal Fixed Pulse Mode 9 Reference the table below when configuring each Analog Input Configuration Register MWnn60 MWnn63 Input Signal Type Register Value V...

Page 23: ...Type Register Value Voltage 0 to 10V 2 Voltage 0 to 5V 1 Current 4 to 20mA 5 Current 0 to 20mA 6 Analog expansion modules have an analog output resolution of 12 bits with values ranging from 0 4095 Ex...

Page 24: ...HMC3 M0808P0401T 24 HMC3000 Series I O Module Guide 24 Analog Input Voltage Analog Input Current Analog Input mV Thermocouple Analog Input RTD...

Page 25: ...HMC3 M0808P0401T 25 HMC3000 Series I O Module Guide 25 Analog Output Voltage Analog Output Current HSC Single Phase Up Counter HSC Single Phase Down Counter HSC Quadrature...

Page 26: ...HMC3 M0808P0401T 26 HMC3000 Series I O Module Guide 26...

Page 27: ...h are high speed inputs It also has eight outputs two sourcing PNP which can be configured for PWM operation and the other 6 are relay type This module also has 4 universal analog inputs Voltage Curre...

Page 28: ...0KHz Minimum ON Output Voltage 22 VDC Maximum ON Output Voltage 30 VDC Minimum OFF Output Voltage 0 2 VDC Maximum OFF Output Voltage 1 VDC Rated Load 250mA 24VDC 2A 230VAC Nominal load 96 6W resistive...

Page 29: ...ite HSC Reset Bit Mnn081 Mnn177 Read Write Output Flag Y2 Y3 PWM Outputs Channel 1 Channel 2 Output Y0 Y1 Read Only PWM Configuration Register MWnn24 MWnn30 Read Write Frequency Setting Register MWnn2...

Page 30: ...Pulse Direction variable frequency 8 Trapezoidal Fixed Pulse Mode 9 Reference the table below when configuring each Analog Input Configuration Register MWnn60 MWnn63 Input Signal Type Register Value V...

Page 31: ...Type Register Value Voltage 0 to 10V 2 Voltage 0 to 5V 1 Current 4 to 20mA 5 Current 0 to 20mA 6 Analog expansion modules have an analog output resolution of 12 bits with values ranging from 0 4095 Ex...

Page 32: ...HMC3 M0808Y0401T 32 HMC3000 Series I O Module Guide 32 Analog Input Voltage Analog Input Current Analog Input mV Thermocouple Analog Input RTD...

Page 33: ...HMC3 M0808Y0401T 33 HMC3000 Series I O Module Guide 33 Analog Output Voltage Analog Output Current HSC Single Phase Up Counter HSC Single Phase Down Counter HSC Quadrature...

Page 34: ...HMC3 M0808Y0401T 34 HMC3000 Series I O Module Guide 34...

Page 35: ...This module also has two analog inputs each measuring Voltage or Current Specifications Power 12 VDC from base Certifications CE UL Digital Inputs 12 bidirectional inputs 2 high speed pairs Rated Inpu...

Page 36: ...um OFF Output Voltage 1 VDC Rated Load 250mA 24VDC Nominal load 96 6W resistive 24VDC 6VA inductive UPF High speed Channels No of inputs 2 channel pairs X0 X1 and X2 X3 Maximum Input Frequency 200 KHz...

Page 37: ...n081 Mnn177 Read Write Output Flag Y2 Y3 PWM Outputs Channel 1 Channel 2 Output Y0 Y1 Read Only PWM Configuration Register MWnn24 MWnn30 Read Write Frequency Setting Register MWnn25 MWnn31 Read Write...

Page 38: ...e 9 Reference the table below when configuring each Analog Input Configuration Register MWnn60 MWnn61 Input Signal Type Register Value Voltage 0 to 10V 1 Voltage 0 to 5V 6 Current 4 to 20mA 2 Current...

Page 39: ...HMC3 M1212P0200 39 HMC3000 Series I O Module Guide 39 Wiring Digital Inputs Digital Outputs Analog Input Voltage Analog Input Current...

Page 40: ...HMC3 M1212P0200 40 HMC3000 Series I O Module Guide 40 HSC Single Phase Up Counter HSC Single Phase Down Counter...

Page 41: ...HMC3 M1212P0200 41 HMC3000 Series I O Module Guide 41 HSC Quadrature...

Page 42: ...e other 10 outputs are relay type This module also has two analog inputs each measuring Voltage or Current Specifications Power 12 VDC from base Certifications CE UL Digital Inputs 12 bidirectional in...

Page 43: ...m OFF Output Voltage 1 VDC Rated Load 250mA 24VDC 2A 230VAC Nominal load 96 6W resistive 24VDC 6VA inductive UPF High speed Channels No of inputs 2 channel pairs X0 X1 and X2 X3 Maximum Input Frequenc...

Page 44: ...n081 Mnn177 Read Write Output Flag Y2 Y3 PWM Outputs Channel 1 Channel 2 Output Y0 Y1 Read Only PWM Configuration Register MWnn24 MWnn30 Read Write Frequency Setting Register MWnn25 MWnn31 Read Write...

Page 45: ...e 9 Reference the table below when configuring each Analog Input Configuration Register MWnn60 MWnn61 Input Signal Type Register Value Voltage 0 to 10V 1 Voltage 0 to 5V 6 Current 4 to 20mA 2 Current...

Page 46: ...HMC3 M1212Y0200 46 HMC3000 Series I O Module Guide 46 Wiring Digital Inputs Digital Outputs Analog Input Voltage Analog Input Current...

Page 47: ...HMC3 M1212Y0200 47 HMC3000 Series I O Module Guide 47 HSC Single Phase Up Counter HSC Single Phase Down Counter...

Page 48: ...HMC3 M1212Y0200 48 HMC3000 Series I O Module Guide 48 HSC Quadrature...

Page 49: ...uts are PWM This module also has two analog inputs Voltage Current and one analog output Voltage Current Specifications Power 12 VDC from base Certifications CE UL Digital Inputs 12 bidirectional inpu...

Page 50: ...inductive UPF Analog Outputs 1 configurable as 0 to 5V 0 to 10V 0 to 20mA 4 20mA Accuracy Overall Accuracy 0 2 of full scale 25 C max Load 1 K Min for V 500 Max for mA Output Resolution 12 bit High sp...

Page 51: ...Read Only PWM Configuration Register MWnn24 MWnn30 Read Write Frequency Setting Register MWnn25 MWnn31 Read Write ON Duty Setting Register Duty Cycle MWnn27 MWnn33 Read Write Pulse Enable Flag Mnn576...

Page 52: ...o 10V 1 Voltage 0 to 5V 6 Current 4 to 20mA 2 Current 0 to 20mA 3 The values in the appropriate analog input register range from 0 64000 with over and under indications at 65000 and 65001 while analog...

Page 53: ...HMC3 M1210P0201 53 HMC3000 Series I O Module Guide 53 Wiring Digital Inputs Digital Outputs Analog Input Voltage Analog Input Current...

Page 54: ...HMC3 M1210P0201 54 HMC3000 Series I O Module Guide 54 Analog Output Voltage Analog Output Current HSC Single Phase Up Counter...

Page 55: ...HMC3 M1210P0201 55 HMC3000 Series I O Module Guide 55 HSC Single Phase Down Counter HSC Quadrature...

Page 56: ...HMC3 M1210P0201 56 HMC3000 Series I O Module Guide 56...

Page 57: ...ility and 8 are relay type This module also has two analog inputs Voltage Current and one analog output Voltage Current Specifications Power 12 VDC from base Certifications CE UL Digital Inputs 12 bid...

Page 58: ...4VDC 6VA inductive UPF Analog Outputs 1 configurable as 0 to 5V 0 to 10V 0 to 20mA 4 20mA Accuracy Overall Accuracy 0 2 of full scale 25 C max Load 1 K Min for V 500 Max for mA Output Resolution 12 bi...

Page 59: ...Read Only PWM Configuration Register MWnn24 MWnn30 Read Write Frequency Setting Register MWnn25 MWnn31 Read Write ON Duty Setting Register Duty Cycle MWnn27 MWnn33 Read Write Pulse Enable Flag Mnn576...

Page 60: ...o 10V 1 Voltage 0 to 5V 6 Current 4 to 20mA 2 Current 0 to 20mA 3 The values in the appropriate analog input register range from 0 64000 with over and under indications at 65000 and 65001 while analog...

Page 61: ...HMC3 M1210Y0201 61 HMC3000 Series I O Module Guide 61 Wiring Digital Inputs Digital Outputs Analog Input Voltage Analog Input Current...

Page 62: ...HMC3 M1210Y0201 62 HMC3000 Series I O Module Guide 62 Analog Output Voltage Analog Output Current HSC Single Phase Up Counter...

Page 63: ...HMC3 M1210Y0201 63 HMC3000 Series I O Module Guide 63 HSC Single Phase Down Counter HSC Quadrature...

Page 64: ...pedance 4 9K ohms Minimum ON voltage 15 VDC Maximum OFF voltage 5 VDC Turn ON Time 10 mSec Turn OFF Time 10 mSec Isolation Optically isolated from internal circuit Digital Outputs 14 outputs 12 Relay...

Page 65: ...Channel 2 Output Y0 Y1 Read Only PWM Configuration Register MWnn24 MWnn30 Read Write Frequency Setting Register MWnn25 MWnn31 Read Write ON Duty Setting Register Duty Cycle MWnn27 MWnn33 Read Write P...

Page 66: ...HMC3 M1614Y 66 HMC3000 Series I O Module Guide 66 Wiring Digital Inputs Digital Outputs HSC Single Phase Up Counter...

Page 67: ...HMC3 M1614Y 67 HMC3000 Series I O Module Guide 67 HSC Single Phase Down Counter HSC Quadrature...

Page 68: ...ohms Minimum ON voltage 15 VDC Maximum OFF voltage 5 VDC Turn ON Time 10 mSec Turn OFF Time 10 mSec Isolation Optically isolated from internal circuit Digital Outputs 16 sourcing outputs PNP type 2 PW...

Page 69: ...Channel 2 Output Y0 Y1 Read Only PWM Configuration Register MWnn24 MWnn30 Read Write Frequency Setting Register MWnn25 MWnn31 Read Write ON Duty Setting Register Duty Cycle MWnn27 MWnn33 Read Write P...

Page 70: ...HMC3 M1616P 70 HMC3000 Series I O Module Guide 70 Wiring Digital Inputs Digital Outputs HSC Single Phase Up Counter...

Page 71: ...HMC3 M1616P 71 HMC3000 Series I O Module Guide 71 HSC Single Phase Down Counter HSC Quadrature...

Page 72: ...HMC3 M1616P 72 HMC3000 Series I O Module Guide 72...

Page 73: ...Maple Systems Inc 808 134th St SW Suite 120 Everett WA 98204 425 745 3229 Your Industrial Control Solutions Source _____________________ www maplesystems com 1010 1056 Rev 04...