Product Description:
HMC4043A-M
: 4.3”, 480 x 272 pixels, WQVGA color TFT
with 4-wire analog resistive touch screen with 2 serial
ports*, one USB Device port & 1 USB Host port. It supports
1 expansion module.
* Refer to the communication section for more details.
Contents:
1ea HMC4043A-M (bagged and sealed)
1ea Mounting kit (4ea mounting clips)
1ea Input Power connector plug
1ea Quick Strat Guide
Perform the following steps to configure and use the
HMC4000 Series unit:
1. Install MAPware-7000 software.
2. Create your project.
3. Connect a programming cable (USB or Ethernet).
4. Save your project.
5. Download project to HMC4043 (note: you must select
the Download Firmware option for the initial download).
6. The HMC4000 unit is ready to use in the system.
Power (Base)
24VDC(+20%, -15%), 160mA, 3.84W
Power
(With 1 Expansion)
24VDC(+20%, -15%), 210mA, 5.04W
Display
4.3” WQVGA color TFT with 4-wire analog resistive
touch screen
LEDs
1
RAM Memory
512MB
User Application
Up to 1GB that includes user application, data log,
alarms, retentive memory and logic memory
eMMC
4GB
RTC
Built-in, date and time function
Expansion
It supports 1 expansion slot
Weight
Approx. 400gm
Panel Cutout
111.00mm(W) x 80.00mm(H)
Product
Dimensions
120.00mm(W) x 89.0mm(H) x 31.5mm(D)
Communication
Serial Port*
1 x RS232, RS485
USB Ports
1 USB Device and 1 USB Host
Ethernet
1 Ethernet Port
SD Card
Micro SD [High Capacity (4GB to 32GB)]
Speed Class:
[While inserting and removing SD card, please make
sure to TURNOFF the power to the unit.]
Environment & Approvals
Operating
Temperature
0° to 50°C
Storage
Temperature
-20° to 85°C
Humidity
10 to 90% (Non-Condensing)
Shock
IEC 60068-2-27
25g, 11ms, 6 shocks per axis, total 18 shocks (X, Y,
Z)
Vibration
IEC 60068-2-6
5 to 150Hz, 3g peak (X, Y, Z)
EMC
EN 55011 : 2009/A1 : 2010
EN 61131-2 : 2007
EN 61000-6-2 : 2005/AC : 2005
EN 61000-6-4 : 2007/A1 : 2011
Protection
IP66 for front panel mounting
APPROVALS
CE, UL (Class1 Div2) & RoHS
[
* Note:
HMC4043A-M support one DB9 port that supports RS232 & RS485
levels on different pins. “Y” type cable can be used for separate RS232 and
RS485 levels simultaneously.]
(Part No.: 7431-0122)
SPECIFICATIONS
PRODUCT DIMENSIONS
Panel Cutout Dimensions: 111.00 x 80.00mm,
Panel Thickness: Maximum 6mm
Mounting Clamps: 4
QUICK START GUIDE
HMC4043A-M Series
GETTING STARTED
For More Information, visit
AW-10114043AM Rev. 00, 02/18/22