Model: HMC7-MI-02
Phone: 425/745-3229 • Fax: 425/745-3429 • Email: maple@maplesystems.com • www.maplesystems.com
.
Doc. No. 1011-0702
Page 2 of 2
Rev. 03, 09/06/2012
Con�iguration:
Use MAPware-7000 to assign input (XW) and con�iguration
(MW) memory addresses to the module. These addresses are
created according to the slot location of the module, where
nn
refers to the slot number (ex. 01…05):
Register
Description
Access
XWnn00
Input Channel 1 Data
Read Only
XWnn01
Input Channel 2 Data
Read Only
XWnn02
Input Channel 3 Data
Read Only
XWnn03
Input Channel 4 Data
Read Only
MWnn00
Input Channel 1
Con�iguration Register
Read/Write
MWnn01
Input Channel 2
Con�iguration Register
Read/Write
MWnn02
Input Channel 3
Con�iguration Register
Read/Write
MWnn03
Input Channel 4
Con�iguration Register
Read/Write
Reference the table below when con�iguring each Input
Con�iguration Register (MWnn00-MWnn03):
Input Channel
Signal Type
Value
mA (4-20mA)
0
Voltage (0-10V)
1
Voltage (-10 to +10V)
2
mA (0-20mA)
3
Additional Resources:
Detailed instructions on the operation and installation of the
HMC7000 Series are available in the HMC7000 Programming
Manual that is included with the MAPware-7000 con�iguration
software. MAPware-7000 also includes help �iles, which
provide detailed information on using the con�iguration
software.
WARNING: DO NOT REMOVE OR REPLACE WHILE CIRCUIT
IS LIVE UNLESS THE AREA IS KNOWN TO BE FREE OF
IGNITIBLE CONCENTRATIONS OF FLAMMABLE SUBSTANCES.
This equipment is suitable for use in Class I, Division 2, Groups
A, B, C and D or non-hazardous locations only.
WARNING – EXPLOSION HAZARD – Do not disconnect
equipment unless power has been removed or the area is
known to be non-hazardous.
WARNING – EXPLOSION HAZARD - Substitution of
components may impair suitability for Class I, Division 2.
It is recommended that the user periodically inspect the sealed
devices used, check for any degradation of properties, and
replace as necessary.
For Technical Support:
Please contact Maple Systems if you have any questions
regarding this product. We ask that you provide us with the
unit serial number and �irmware revision number written on
the product label of the unit.
Maple Systems Inc.
808 134
th
St. SW, STE 120
Everett, WA 98204
Tel: 425-745-3229
Fax: 425-745-3429
Email: support@maplesystems.com
Website: www.maplesystems.com