background image

Quick Start Guide  

 

 

 

 

 

 

 

 

 

 

 

   

            

             

    HMC7-MIO-08 

 

                                                                                       Maple Systems Inc., 808 134th Street SW, Suite 120, Everett, WA 98204-7333 • www.maplesystems.com                                                                  

.

 

Doc. No. 1011-0715 

                                           

           

Page 1 of 2 

 

 

 

 

 

                                        Rev. 05, 05/18/2016 

 

 

Description:  

HMC7-MIO-08 I/O expansion module with four universal 

analog inputs and two analog outputs. 

Contents: 

 

One HMC7-MI0-08 (in plastic bag ) 

 

Quick Start Guide 

Programming software (MAPware-7000), cables, and power 
supply purchased separately. 

 

Specifications:

 

Power:    

3.9VDC from HMC7000 base 

 

 

24VDC 80mA max user supplied 

Analog Inputs:  

Four (Voltage, Millivolts, Current, 

RTD(PT100( α1, α2), PT1000) and 
Thermocouple (TYPE J, K) 

Resolution: 

 

16 bit 

Voltage Ranges:   

0 to 10 V, 0 to 5 V, -10 to +10V 

Millivolt Ranges:   

0-100mV, 0-50mV 

RTD Ranges: 

 

PT100 α1: -200 to 850°C 

 

 

 

PT100 α2: -100 to 457°C 

 

 

 

PT1000: -200 to 850°C 

Thermocouple Ranges: 

Type J: -210 to 1200°C 

 

 

 

Type K: -200 to 1373 °C 

 

Input Impedance:   

1 MΩ (V,mV, TC, RTD) 

 

 

 

100Ω (mA) 

Maximum Input:   

+/- 30 VDC, 30mA 

Accuracy: 

 

1% of full scale 

 

Analog Outputs: 

2 (0 to 5V, 0 to 10V; 0 to 20mA, 4-20mA) 

Resolution: 

 

16 bit 

Accuracy: 

 

1% of full scale 

Load:   

 

1 KΩ (Min) for V 

 

 

 

500Ω (Max) for mA 

Connection Method:  Removable terminals (3.81 mm pitch) 
Operating Temp: 

0 to 55° C 

Humidity:  

10% to 90% (non-condensing) 

Dimensions: 

3.11 x 1.18 x 1.42 inches  

[79x30x36mm] 

 

Dimensional Details:

 

                   

 

 

Mounting Module to HMC7000: 

The HMC7 I/O module must be mounted onto the back of a 
HMC7000 Series unit using one of the HMC expansion ports. 

When locating equipment behind the HMC7000 ensure that AC 

power wiring, PLC output modules, contactors, starters, relay 

and any other source of electrical interference are located 

away from the HMC7000. Make sure that variable speed drives 

and switching power supplies are located away from the unit.

 

         

     Step 1                 Step 2 

      Step 3                                      

 

 

 

Step 1: Pull the two white lock connectors out from the center 

of the module. 

 

Step 2: Place the module onto the HMC7000 expansion port so 

that the I/O module interconnect plug can attach to the 
HMC7000 socket.  Note: remove the protective tab on the 

HMC7000 expansion port to expose the socket. 

 

Step 3: Push down the lock connectors to safely secure the I/O 

Expansion module. 

 

Wiring I/O Expansion Modules: 

The HMC7 I/O module has green block terminals that are used 
to wire the module to the digital input devices (i.e. switches, 

contacts, etc).  The block terminals can be physically removed 

from the module to facilitate connection (18-gauge wire 

recommended).  Note: A 3/32” flat blade screwdriver should be 

used to tighten the screws of the terminal block. 

 
Note: 24VDC must be supplied to the pins as marked or the 

module will not be recognized by the HMC or function. 

 

Connection for analog voltage inputs: 

             

 

 

Connection for analog current inputs: 

                      

 

 