HMC7000 Series I/O Module Guide
55
HMC7000 Series I/O Module Guide
55
Configuration:
Use MAPware-7000 to assign input (X and XW), output (Y and YW), and configuration (M and MW) memory
addresses to the module. These addresses are created according to the slot location of the module, where nn
refers to the slot number
(ex. 01…05):
Function
Register
Access
X0-X7 Inputs
Xnn000-007 (XWnn00)
Rd Only
Y0-Y7 Outputs
Ynn000-007 (YWnn00)
Rd/Write
High Speed Counter
Option
HSC Ch. 1
HSC Ch. 2
HSC Ch. 3
HSC Ch. 4
HSC Input
X0 (terminal)
Xnn000 (reg)
X5 (terminal)
Xnn005 (reg)
X2 (terminal)
Xnn002 (reg)
X7 (terminal)
Xnn007 (reg)
Rd Only
HSC Reset Input
X1 (terminal)
Xnn001 (reg)
X6 (terminal)
Xnn006 (reg)
X3 (terminal)
Xnn003 (reg)
X4 (terminal)
Xnn004 (reg)
Rd Only
HSC Output Flag
Y1 (terminal)
Ynn001 (reg)
Y6 (terminal)
Ynn006 (reg)
Y7 (terminal)
Ynn007 (reg)
Y0 (terminal)
Ynn000 (reg)
Rd/Write
HSC Configuration
Register
MWnn00
MWnn06
MWn112
MWn118
Rd/Write
HSC Counter Register
(Current Value)
MWnn01
MWnn02
MWnn07
MWnn08
MWnn13
MWnn14
MWnn19
MWnn20
Rd/Write
HSC Preset Register
MWnn03
MWnn04
MWnn09
MWnn10
MWnn15
MWnn16
MWnn21
MWnn22
Rd/Write
HSC Enable Bit
Mnn080
Mnn176
Mnn272
Mnn368
Rd/Write
HSC Reset Bit
Mnn081
Mnn177
Mnn273
Mnn369
Rd/Write
Quadrature Inputs
Pair 1
Pair 2
Counter Inputs
X0, X5
X2, X7
Rd Only
Counter Reset Input
X1
X3
Rd Only
Output Flag
Y1
Y7
Rd/Write
PWM Outputs
PWM1
PWM2
Output
Y2
Y4
Rd Only