background image

 

Model: HMC7043A-M 

 

                                                                         Phone: 425/745-3229 • Fax: 425/745-3429 • Email: maple@maplesystems.com • www.maplesystems.com                                                                                  

.

Doc. No. 1011-7043AM 

                                           

           

Page 2 of 2 

 

 

 

 

 

 

                   Rev. 00, 10/01/2013 

Getting Started: 

Perform the following steps to configure and use the HMC7000 

Series unit: 

1.

 

Install MAPWare-7000 software. 

2.

 

Create your project. 

3.

 

Connect a programming cable (USB preferred). 

4.

 

Save your project. 

5.

 

Download project to HMC7000 (note: you must 

select the Download Firmware option for the initial 

download). 

6.

 

The HMC7000 unit is ready to use in the system. 

 

PC Requirements for MAPware-7000: 

Processor: 1GHz Pentium-based processor or equivalent 

Operating System: Microsoft Windows XP Professional, 2000, 

Vista, Windows 7 or Windows 8.

 

RAM: 1 GB 

Hard Disk: 800 MB (including 200MB for the .NET framework 
redistributable) 

Display: 1024x768 high color 16-bit 

Mouse/Keyboard: Required 

USB / Ethernet port: for project downloads 

 

Installing the Software: 

1.

 

Insert MAPware-7000 CD into CD-ROM drive and 

follow instructions. 

2.

 

If software installation does not automatically start 

click \ SETUP.EXE from CD directory. 

 

PLC Connecting Cables:   

Contact Maple Systems to order any PLC Communications 

Cables or to download a cable pinout diagram. 

 

Additional Resources:   

Detailed instructions on the operation and installation of the 
HMC7000 Series are available in the HMC7000 Programming 

Manual that is included with the MAPware-7000 configuration 

software.  MAPware-7000 also includes help files which 

provide detailed information on using the configuration 

software. 

 
Other Sources (visit Maple Systems Support Center): 

 

Controller Information Sheets- Specific information on 
connecting a particular manufacturer's PLC to the 

HMC7000 

 

Cable Drawings-  wiring diagrams to particular PLCs 

 

Technical Notes- Provides additional information and 
examples not covered in the operations manual 

 

Software Upgrades- Upgrades to the MAPware-7000 
software 

 

 

 

 

 

 

Class I Division 2 Wiring Considerations: 
 

 

 

Capacitance and inductance of field wiring from intrinsically 
safe equipment to the associated apparatus must be included 

in the system calculations as shown in Table 1.  Cable 

capacitance, C

cable

, plus intrinsically safe equipment 

capacitance, C

i

, must be less than the marked capacitance, C

a

 

(or C

o

), shown on any associated apparatus used.  The same 

applies for inductance (L

cable

, L

i

 and L

a

 or L

o

, respectively).  

Where the cable capacitance and inductance per foot are not 

known, the following values shall be used: C

cable

 = 60 pF/ft, 

L

cable

 = 0.2 

μ

H/ft. 

 

TABLE 1: 

I.S. Equipment 

Associated Apparatus 

V

max

 (or U

i

)  > 

V

oc

 or V

t

 (or U

o

I

max

 (or I

i

)   > 

I

sc

 or I

t

 (or I

o

C

i

 + C

cable

     < 

C

a

 (or Co) 

L

i

 + L

cable

     < 

L

a

 (or L

o

 

Wiring method must be in accordance with ANSI/NFPA70 
Associated apparatus may be in a Division 2 or Zone 2 location 

if so approved.  

Associated apparatus must be installed in accordance with its 

manufacturer’s control drawing and National Electrical Code 

for installation in the United States and Canadian Electrical 

Code for installation in Canada. 
 

 

 

 

 

 
 

 

 

 

 

 

WARNING: DO NOT REMOVE OR REPLACE WHILE CIRCUIT 

IS LIVE UNLESS THE AREA IS KNOWN TO BE FREE OF 

IGNITIBLE CONCENTRATIONS OF FLAMMABLE SUBSTANCES. 
This equipment is suitable for use in Class I, Division 2, Groups 

A, B, C and D or non-hazardous locations only. 

 

WARNING – EXPLOSION HAZARD – Do not disconnect 

equipment unless power has been removed or the area is 

known to be non-hazardous. 

 

WARNING – EXPLOSION HAZARD - Substitution of 

components may impair suitability for Class I, Division 2. 

 

WARNING - CAUTION, battery may explode if mistreated. 

Do not recharge, disassemble or dispose of in fire. 

 

WARNING - Replace battery with Type CR1225FH-LF, 

manufactured by Renata SA, only. Use of another battery may 

present a risk of fire or explosion. See owner's manual for 

safety instructions. 

 

It is recommended that the user periodically inspect the sealed 

devices used, check for any degradation of properties, and 

replace as necessary.  
 

 

 

 

 

 
 

 

 

 

 

 
 

 

 

 

 

For Technical Support: 

Please contact Maple Systems if you have any questions 

regarding this product.  We ask that you provide us with the 
unit serial number and firmware revision number written on 

the product label of the unit.   If applicable, please provide us 

with the type of PLC used in your application.  

 

Maple Systems Inc. 

808 134

th

 St. SW, STE 120 

Everett, WA  98204 

Tel: 425-745-3229 

Fax: 425-745-3429 

Email: support@maplesystems.com 

Website: www.maplesystems.com 

Hazardous Location 

Class I Division 2 

Groups A, B, C, and D 

Non-Hazardous 

Location 

HMC7043 

USB Port 

JP9 

V

max

=3.3 VDC 

I

max

=150 mA 

L

i

=0 

C

i

=9pF 

Associated Apparatus 

USB Port 

 

V

oc

<3.3 VDC 

I

sc

<2.2 mA 

L

a

>L

i

 + L

cable 

C

a

>C

i

 + C

cable 

Reviews: