background image

HMI5000L Installation Guide                                                                                                5

1010-1018 Rev 13                                                                          www.maplesystems.com

Cable Routing and Noise Immunity

Follow these guidelines when routing cables to the HMI:

Always route the HMI communication cable and the power cable 
away from any AC voltage or rapidly switching DC control lines.

Never bundle the HMI cables together with 120VAC power wires 
or with relay wiring.

Try to keep at least 8 inches (20 cm) of separation between the 
HMI cables and other power wiring. If voltages greater than 
120VAC are used in the system, greater separation is required.

If the HMI cables must come near AC wiring, make sure they 
cross at 90 degrees.

Run AC power wires in a separate grounded conduit to reduce 
electrical noise interference.

Keep the cable lengths for the HMI as short as possible. Do not 
coil excess cable and place it next to AC powered equipment.

Cover any equipment used in the enclosure that operates at high 
frequency or high current levels with a grounded metal shield.

Power Supply Selection 

The power supply used to power the HMI should provide an output of at 
least 

+24 VDC ±20%

 measured at the HMI power connector 

(

HMI5043Lv2, HMI5043LBv2 should be powered with +22~28VDC only

, and 

HMI5043DL should be powered with

 

+10.5~28VDC only

).

A DC regulated power supply 

dedicated to the HMI

 is recommended. 

Use a power supply with adequate current rating for the provided 
voltage. A power line filter installed at the AC input to the HMI power 
supply is highly recommended as a safeguard against conducted RF 
noise, which is often present on factory power lines. The wires 
connecting the output of the power line filter to the power supply should 
be kept as short as possible to minimize any additional noise pickup. The 
case of the power line filter should be connected to a quiet earth ground. 
The power line filter should have a current rating of at least 3 Amps with 
common mode and differential mode attenuation. 

In applications that may have high frequency noise present, a resistor 
(~1 

MΩ)

 and capacitor (~4700 pF) should be used in parallel to clean 

earth ground on the DC output of the power supply.

Do not use the power supply used to provide power to the HMI to power 
switching relays, solenoids, or other active devices.

Summary of Contents for HMI5043DL

Page 1: ...ies touchscreens are configured using the EasyBuilder Pro Software For information on programming and configuring the HMI please refer to the EasyBuilder Pro Programming Manual available for free download on the Maple Systems website in the Support Center For additional information please refer to the Support Center section of the Maple Systems website www maplesystems com support The Support Cent...

Page 2: ...ll material in the container against the packing list Maple Systems will not accept responsibility for shortages against the packing list unless notified within 30 days The equipment and accessories were inspected and tested by Maple Systems before shipment Examine the equipment carefully if any shipping damage is evident notify the carrier immediately Maple Systems is not responsible for claim ne...

Page 3: ...pliance The HMIs have been tested to conform to European CE requirements which meet or exceed the noise emissions and immunity requirements as set forth in the EN55022 Emissions and EN55024 Immunity standards The products are designed to withstand electrical noise in harsh industrial environments They also conform to requirements that limit electrical emissions However this does not guarantee that...

Page 4: ...ational electrical standards when installing the HMI Failure to comply with these restrictions could result in loss of life serious personal injury or equipment damage Warning Do not connect the HMI to an AC power source This will cause permanent damage to the HMI Warning A Hard wired EMERGENCY STOP should be fitted in any system using an HMI to comply with ICS Safety Recommendations Warning Do no...

Page 5: ...upply used to power the HMI should provide an output of at least 24 VDC 20 measured at the HMI power connector HMI5043Lv2 HMI5043LBv2 should be powered with 22 28VDC only and HMI5043DL should be powered with 10 5 28VDC only A DC regulated power supply dedicated to the HMI is recommended Use a power supply with adequate current rating for the provided voltage A power line filter installed at the AC...

Page 6: ...nd strap Quiet ground isolated AC Power Line Filter HMI Power Supply Shielded power cable Control panel is tied to a reliable earth ground 2 1 3 4 5 rear side HMI5100L 1 rear side HMI5070L 2 2 3 1 Also HMI5102L HMI5103L HMI5120XL HMI5121XL and HMI5150XL 2 Also HMI5043Lv2 HMI5043LBv2 HMI5043DL HMI5070DL HMI5070LB HMI5070NL HMI5071L HMI5097DXL and HMI5097NXL ...

Page 7: ...ground Note If the control panel is made of a non conductive material it is essential that the chassis ground terminal of the HMI is connected to a clean earth ground point located close to the panel Connect the power cable s shield wire to the HMI s chassis ground terminal Connect the control panel to earth ground using a copper grounding rod close to the HMI and control panel Hinged doors on con...

Page 8: ... the power cable from the HMI to the power supply The power cable should not be any longer than necessary 2 Install the cable wires referencing the chart below with colors shown for Maple Systems Cable 6030 0009 a Strip the power cable shield to expose 2 of the black and red wires b Strip about of insulation from the black and red wires c Connect the red wire to the positive input of the HMI power...

Page 9: ...hes pits and other features that prevent the gasket from sealing properly If the panel or mounting surface is not uniform thick flat stiff or smooth enough then a sealant such as silicone may be required Note Clean and deburr the panel cutout before the HMI is installed Mount the HMI to the Panel Note The clamps for some models may be slightly different than shown here but operate essentially the ...

Page 10: ... included with the EasyBuilder Pro software must be installed when downloading from the PC to the HMI via USB connection Caution When connecting two powered devices via USB a difference in potential can exist between the ground reference on each device If there is a difference in ground potential voltage making a connection via a USB cable can complete a ground loop that may damage the HMI and PC ...

Page 11: ... arrow icon located in the lower right corner of the screen 3 Click the gear icon to enter the system settings menu 4 When prompted enter the system password default 111111 5 Navigate to the Network tab 6 Enter the desired IP address or select Obtain an IP Address Automatically to enable DHCP 7 Click Apply to save the changes and OK to exit the system settings menu 8 The updated IP address will ap...

Page 12: ...PEN Hide System Toolbar OPEN OPEN SHORT OPEN Boot Loader mode OPEN OPEN OPEN SHORT Reserved OPEN OPEN OPEN OPEN Normal operation Note Place a jumper cap between the respective header pins to set the jumper mode HMI Power must be cycled to enable the selected DIP switch or jumper mode Touchscreen Calibration mode This mode allows calibration of the touchscreen This mode can also be entered by press...

Page 13: ...r up remove power An internal fuse except 4 3 display models will prevent damage if the polarity of the DC power is incorrect Check wiring to ensure proper connections and try to power up again USB Stick Clamp not on all models The USB Stick Clamp prevents a USB stick from disconnecting from the HMI due to vibration Steps 1 Insert the USB stick connector into the clamp and secure with the included...

Page 14: ... wire RS COM3 1 RX DATA 2 RX DATA 3 TX 4 TX 5 GND 6 TXD 7 DATA 8 DATA 9 RXD Pin COM1 232 RS 1 2 RXD 3 TXD 4 5 GND 6 7 RTS 8 CTS 9 HMI XL 5150 DE9S DE9P HMI5100L HMI HMI LB 5070L 5070 HMI XL 5121 Pin COM1 485 2 wire RS COM1 485 4 wire RS COM3 485 2 wire RS 1 DATA RX 2 DATA RX 3 TX 4 TX 5 GND COM 1 6 7 DATA 8 DATA 9 GND COM 3 HMI 0XL 512 Note COM1 RS 485 2W and COM3 RS 485 2W support the Siemens MPI...

Page 15: ... 485 4W RS COM2 COM3 485 2W RS RS 485 4W COM3 1 DATA RX 2 DATA RX 3 TX 4 TX 5 GND 6 DATA RX 7 DATA TX 8 DATA TX 9 DATA RX Pin COM1 RS 232 232 RS COM3 1 2 RXD 3 TXD 4 5 GND 6 7 RTS TXD 8 CTS RXD 9 GND Pin COM1 RS 485 2W COM2 485 2W RS COM2 485 4W RS 485 2W RS COM3 COM3 RS 485 4W Note COM1 RS 485 2W and COM3 RS 485 4W available on HMI5102L and HMI5103L units manufactured after July 2018 with OS vers...

Page 16: ...3 Enter the desired IP address or select Obtain an IP Address Automatically to enable DHCP 4 Navigate to the LAN2 tab 5 Enter the desired IP address or select Obtain an IP Address Automatically to enable DHCP Note LAN1 and LAN2 must be on separate subnets in order for both ports to operate simultaneously 6 Click Apply to save the changes and OK to exit the system settings menu 7 The updated IP add...

Page 17: ...in addition to the standard RJ45 Ethernet port Supported Wi Fi modes are IEEE 802 11 b g n with WPA PSK WPA2 PSK encryption Wi Fi is off by default To enable and configure Wi Fi 1 Enter the System Settings menu 2 Navigate to the Wireless tab 3 Enter the desired IP address or select Obtain an IP Address Automatically to enable DHCP 4 Select the Wi Fi Setting button ...

Page 18: ... 10 Tap Close to exit the Wi Fi setting window 11 Click Apply to save the changes and OK to exit the system settings menu 12 The updated IP addressing will appear in the Wi Fi tabs of the System Information window also accessed via the arrow icon Note When using the Wi Fi simultaneously with the wired Ethernet port ensure that the connections are on different subnets Detailed instructions of the H...

Page 19: ......

Page 20: ...v 13 www maplesystems com 2022 Maple Systems Inc All rights reserved Maple Systems Inc 808 134th Street SW Suite 120 Everett WA 98204 7333 Phone 425 745 3229 Email support maplesystems com Web www maplesystems com ...

Reviews: