4
To create a Word Lamp Object
1.
From the Objects
menu, click
Lamp-Word Lamp
. Or click the
Word Lamp
icon in the
Part1 toolbar. The Create Word Lamp Object dialog box appears.
2.
Use the Description: box to enter a
title
for the Word Lamp part. A description is not
necessary but does help you identify the purpose of the part.
3.
Mode: Sets how the object determines the state.
Value
The state of the object is the value in the specified Read Address
LSB:
Note: This mode will
not work correctly when
data
is
32-bit float
The state of the object is determined by the first bit that is set in the
value specified by the Read Address:
00000000 state 0
00000001 state 1
00000010 state 2
00000100 state 3
10000000 state 8
If more than one bit is set, the lowest-order bit is used:
00000011
state 1
10001000 state 4
Change State by Time
The state of the object increments automatically at the interval
specified by
Time Interval
. After the last state, the word lamp reverts to
state 0.
4.
In the Read address frame, select the
Device type
from the drop down menu, and then select
the PLC register address.
5.
In the
No. of states:
box, select from 1 to 256 states. If the actual value in the PLC register is
out-of-range for the number of states specified, then no shape or bitmap is displayed.
1010-1007, Rev 05
Rep re senting Data with Graph ics Ob jects
177
Summary of Contents for Silver Plus Series
Page 20: ...1010 1007 Rev 05 16 Silver Plus Series Installation Operation Manual ...
Page 31: ...COM Ports for the HMI5056 5070 1010 1007 Rev 05 Connect the OIT to the PLC or Controller 27 ...
Page 38: ...1010 1007 Rev 05 34 Silver Plus Series Installation Operation Manual ...
Page 49: ...7 Click the Shape tab 1010 1007 Rev 05 Creating Your First Project 45 ...
Page 62: ...1010 1007 Rev 05 58 Silver Plus Series Installation Operation Manual ...
Page 75: ...3 Click OK The System Parameter Settings dialog appears 1010 1007 Rev 05 Using EZware 5000 71 ...
Page 132: ...1010 1007 Rev 05 128 Silver Plus Series Installation Operation Manual ...
Page 156: ...1010 1007 Rev 05 152 Silver Plus Series Installation Operation Manual ...
Page 210: ...1010 1007 Rev 05 206 Silver Plus Series Installation Operation Manual ...
Page 216: ...1010 1007 Rev 05 212 Silver Plus Series Installation Operation Manual ...
Page 246: ...1010 1007 Rev 05 242 Silver Plus Series Installation Operation Manual ...