Value
The state of the object is the value in the specified Read Address.
LSB:
Note: This Mode will not work correctly when the
data format is
32-bit float
The state of the object is determined by the first bit that is set in the
value specified by the Read Address:
00000000 state 0
00000001 state 1
00000010 state 2
00000100 state 3
10000000 state 8
If more than one bit is set, the lowest-order bit is used:
00000011 state 1
10001000 state 4
Change State by Time:
The state of the object increments automatically at the interval
specified by
Time Interval
. After the last state, the word lamp reverts to
state 0
4.
In the Read address frame, select the
Device type
from the drop down menu, and then specify
PLC register
and
type
that the part continuously reads. Select the data format.
5.
In the Write address frame, select the
PLC register address
that the part writes to when
pressed. Select the data format.
6.
In the Attribute frame, select how you want the MultiState Switch object to operate:
Switch Style
Option
Description
JOG+
Increments the PLC register by 1 each time the key is pressed. When the highest state is
reached, the key resets to State 0.
No. of states:
Range: 1 to 255
JOG-
Decrements the PLC register by 1 each time the key is pressed. When the State 0 is
reached, the key resets to the highest state.
No. of states:
Range: 1 to 255
1010-1007, Rev 05
184
Sil ver Plus Se ries In stal la tion & Op er a tion Man ual
Summary of Contents for Silver Plus Series
Page 20: ...1010 1007 Rev 05 16 Silver Plus Series Installation Operation Manual ...
Page 31: ...COM Ports for the HMI5056 5070 1010 1007 Rev 05 Connect the OIT to the PLC or Controller 27 ...
Page 38: ...1010 1007 Rev 05 34 Silver Plus Series Installation Operation Manual ...
Page 49: ...7 Click the Shape tab 1010 1007 Rev 05 Creating Your First Project 45 ...
Page 62: ...1010 1007 Rev 05 58 Silver Plus Series Installation Operation Manual ...
Page 75: ...3 Click OK The System Parameter Settings dialog appears 1010 1007 Rev 05 Using EZware 5000 71 ...
Page 132: ...1010 1007 Rev 05 128 Silver Plus Series Installation Operation Manual ...
Page 156: ...1010 1007 Rev 05 152 Silver Plus Series Installation Operation Manual ...
Page 210: ...1010 1007 Rev 05 206 Silver Plus Series Installation Operation Manual ...
Page 216: ...1010 1007 Rev 05 212 Silver Plus Series Installation Operation Manual ...
Page 246: ...1010 1007 Rev 05 242 Silver Plus Series Installation Operation Manual ...