1
4
.
Specifications
13
.1 120V Models
GENERAL
Rated Capacity:
700VA, 1000 VA, 1500 VA, 2000 VA, 3000 VA with a power factor of 0.7
Technology:
True on-line, double conversion topology with integral automatic bypass
INPUT
Phase:
Single phase plus ground
Input
Voltage
Range:
100V: 7
6-13
0
V
110V: 80-138V 115V: 83.5-140V 120V: 87-140V
Input Power factor: 0.98
Frequency:
50 / 60 Hz Auto sensing
AC Frequency range:
45 - 65 Hz
Synchronization range:
± 3Hz
Input Current
(120V)
:
700VA -5.8A, 1000VA -8.2A, 1500VA -12.4A, 2000VA -16.5A
, 3000VA -25A
Input Protection: Circuit Breaker for overload and short protection
DC Bus Voltage: 700VA - 24V, 1000VA - 36V, 1500VA - 48V, 2000VA - 72V, 3000VA - 96V
OUTPUT
Output Voltage:
100 / 110 / 115 / 120 VAC
Voltage regulation:
± 2%
(700VA - 2000VA) ± 3% (3000VA)
Voltage distortion:
< 5% THD with non-linear loads, < 3% THD with linear loads
Frequency regulation
± 0.25 Hz (while on battery
)
Dynamic response:
± 9 % max from 100% to 20 % or from 20% to 100 % linear load
Overload capacity:
105% for 1
0 seconds
, 1
3
0%
± 10%
for
300 m
sec
Efficiency (
Bypass
Mode):
Greater than 95%
Efficiency (On-line Mode):
Greater than 8
8
%
Crest Factor:
3 : 1
13
.2 230V Models
GENERAL
Rated power:
700VA, 1000 VA, 1500 VA, 2000 VA, 3000 VA with a power factor of 0.7
Technology:
True on-line, double conversion topology with integral automatic bypass
INPUT
Phase:
Single phase plus ground
Input Voltage range: 208V: 152-260V 220V: 160-276V 230V: 167-280V 240V: 174-280V
Input Power factor: 0.98
Input Protection: Circuit Breaker for overload and short protection
Frequency:
50 / 60 Hz Auto-sensing
AC Frequency range:
45 - 65 Hz
Synchronization range:
± 3Hz
Input Current
(230V)
:
700VA - 3A, 1000VA - 4
.4
A, 1500VA -
6.
5A, 2000VA -
8
.7A, 3000VA - 1
3
A
DC Bus Voltage: 700VA - 24V, 1000VA - 36V, 1500VA - 48V, 2000VA - 72V, 3000VA - 96V
OUTPUT
Output Voltage:
208 / 220 / 230 / 240 VAC
Voltage regulation:
± 2%
Voltage distortion:
< 5% THD with non-linear loads, < 3% THD with linear loads
Frequency regulation
± 0.25 Hz (while on battery)
Dynamic response:
± 9 % max from 100% to 20 % or from 20% to 100 % linear load
Overload capacity:
105% for 10 seconds, 130% ± 10% for 300 msec
Efficiency (
Bypass
Mode):
Greater than 95%
Efficiency (On-line Mode):
Greater than 8
8
%
Crest Factor:
3 : 1
18