background image

5.3 Self-Test

Use the self-test to verify both the operation of the UPS and the condition of the battery. To

perform the self-test, press the ON/TEST button more for more than 1 second, but less than 2

seconds, under normal power conditions. During the self-test, the UPS will operate in back-up mode.
NOTE: During the self-test, the load(s) use battery energy. The “ON BATTERY” LED or BACKUP

LCD icon will illuminate indicating the UPS is supplying power.
If the UPS passes the self-test, it will return to normal on-line operation. The “ON BATTERY” LED

or BACKUP LCD icon will turn OFF and the “ON LINE” LED or INV LCD icon will illuminate.
If the UPS fails the self-test, it immediately returns to on-line operation and the “REPLACE

BATTERY” LED or LCD error code will illuminate, however the loads are not affected. Recharge

the battery overnight and perform the self-test again. If the “REPLACE BATTERY” LED or LCD

error code is still illuminated, call tech support for battery replacement instructions.

5.4 Audible Alarm Silencing

To silence the audible alarm, press the “ON/TEST” button for less than one second while the UPS is

in back-up mode. 
NOTE: This function will not work when the UPS is under “Low Battery” or “Overload” conditions.

NOTE: In back-up mode, the UPS will automatically turn OFF if none of the connected loads are active.

5.5 Load Bar Graph

The 5 LED or LCD segment display indicates the power drawn from the UPS by the load. The

number of illuminated LEDs or segments represents the percentage of the UPS's rated capacity

being utilized. For example, if two LEDs or segments are illuminated, the load is drawing between

20% and 40% of the UPS's rated capacity. (See section 3 for location of the display on the front panel) 
If the UPS is overloaded, the “OVERLOAD” LED or LCD error code illuminates and an alarm sounds.

5.6 Battery Charge Bar Graph

The 5 LED or LCD segment display shows the present charge of the UPS's battery as a percentage

of the battery capacity. When all 5 LEDs or segments are illuminated, the battery is fully charged. 
(see section 3 for location of the display on the front panel).

5.7 Cold Start

When the UPS is OFF and there is no utility power available or present, the cold start feature can be

used to apply power to the loads from the UPS  using the battery as the power source. Press the

ON/TEST button until the UPS beeps and powers up.

5.8 Shutdown Mode

In this mode, the UPS ceases supplying power to the load after battery depletion while waiting for

the return of utility power. If utility power is not restored, an external device, such as a server with

 the included software connected to the UPS via the RS-232 interface, can command the UPS to shut

down. This is typically done to preserve battery capacity after the proper shutdown of protected loads. 

13

5. Operation

5.1 Turn-ON

With the UPS plugged in, press the ON/TEST button more than 2 seconds to energize the UPS. It

will perform a self-test each time it is switched ON. 
NOTE: When switched OFF, the UPS will maintain and continue to charge the battery and also

respond to commands received through the computer interface port.

5.2 Turn-OFF

Press and hold the OFF button until the “LINE NORMAL” or “BACKUP” LED turns OFF.

Summary of Contents for Track Series

Page 1: ...USER MANUAL Track Series Line Interactive True Sine Wave Output Uninterruptible Power Supply...

Page 2: ......

Page 3: ..._____________________________ Please take the time to read this manual It provides safety installation and operating instructions that will allow you to derive the maximum performance and service life...

Page 4: ...s a Remove watches rings and other jewelry or metal objects b Use only tools with insulated handles c Wear rubber gloves and boots d Do not lay tools or metal parts on top of batteries e Disconnect ch...

Page 5: ...unctionality 2 4 Installation 8 5 Operation 13 6 Alarms 14 7 Software Options 14 8 Care Maintenance 15 9 Computer Interface Port 15 10 Battery Replacement 16 11 Storage 17 12 Fault Codes 17 13 Trouble...

Page 6: ...reduce the risk of electric shock disconnect the UPS from the main AC supply before installing any interface cables Reconnect the power cord only after the signaling interconnections have been made Th...

Page 7: ...f battery capacity It also displays utility line voltage 3 4 LOAD Bar Graph This LED display shows the power being drawn by the load 3 5 BUCK AVR Indicator YELLOW LED This LED illuminates when the UPS...

Page 8: ...lity line voltage displays 3 12 OFF Button Pressing this button turns OFF the UPS and its connected loads 3 13 SELECT Button Depressing and holding the select button cycles through various LCD display...

Page 9: ...ry in 20 increments 3 20 LOAD LEVEL BAR GRAPH This graph shows how much of the units available capacity is being utilized in 20 increments 3 21 INPUT I P OR OUTPUT O P VOLTAGE Vac Pressing the SELECT...

Page 10: ...INPUT FUSE OUTPUT IN OUT STANDARD 600VA RM MODEL REMOTE PORT IN OUT CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER 3 25 3 29 3 27 EXTENDED RUN TIME RACK MOUNT 3000VA MODEL EXTENDED R...

Page 11: ...ANEL 600 3000VA RM 2U LCD FRONT PANEL 600 3000VA RM 2U REAR VIEW 600 1000VA RM 2U REAR VIEW 1500VA RM 2U REAR VIEW 2000VA RM 2U REAR VIEW 2500 3000VA RM 2U 3 Functionality Front Rear Views 19 Rack Mou...

Page 12: ...e protected receptacle s capacity CAUTION Replace only with same fuse type and rating 3 30 SITE WIRING FAULT INDICATORS RED LED Some Models This LED illuminates when the UPS is connected to an imprope...

Page 13: ...nd the device to be protected telephone modem etc is plugged into the connector labeled OUT NOTE This surge protection device is for indoor use only Never install telephone wiring during a lightning s...

Page 14: ...ery Pack Connection Extended Run Time Models Before connecting ensure that the external battery pack and connector cable are compatible with the UPS Use only the factory supplied external battery conn...

Page 15: ...l Mount Installation The following diagrams illustrate how to install or mount the UPS and battery packs when applicable in either vertical or wall mount applications Vertical Installation Wall mount...

Page 16: ...Mount Installation The following diagrams illustrate how to install or mount the UPS and battery packs when applicable in 19 rack mount applications Lower Slide Rail Installation Rear Bracket Installa...

Page 17: ...Unit Stack Installation The following diagrams illustrate how to stack the units and battery packs when applicable Stacking Units 12...

Page 18: ...the UPS s rated capacity being utilized For example if two LEDs or segments are illuminated the load is drawing between 20 and 40 of the UPS s rated capacity See section 3 for location of the display...

Page 19: ...ase refer to the back of the software CD envelope for installation instructions For operational instrucions install the software launch the program then click HELP in the upper left corner of the soft...

Page 20: ...to the communication port on the back of the UPS a special plug in card may be needed in the event one is not available Some computers may also need special software Contact tech support for details o...

Page 21: ...t the AC power cord from the UPS 3 Remove the two 2 front panel securing screws located on either side of the unit NOTE Some models Remove the two 2 lower front panel screws located on both sides of t...

Page 22: ...cables connected to the computer interface port to avoid draining the battery 11 2 Extended Storage During extended storage in environments where the ambient temperature is 5 to 86 F 15 to 30 C charge...

Page 23: ...anel indicators flash sequentially LED models All indicators are flashing and UPS emits a constant tone UPS operates normally but the site wiring fault indicator is on does not provide expected The UP...

Page 24: ...detection time Efficiency Standby Mode Greater than 95 Overload Capacity 110 for 20 seconds 125 for 5 seconds EXTENDED RUN TIME MODELS GENERAL Rated power 1000 VA 1500 VA 2000 VA 3000 VA with a power...

Page 25: ...e models 32 F to 104 F 0 C to 40 C All standard run time models 32 F to 77 F 0 C to 25 C 3000VA extended run time models Optimum temperature range 59 F to 77 F 15 C to 25 C Storage temperature 5 F to...

Page 26: ...acid 7 2Ah 12V Sealed lead acid 7 2Ah 12V Sealed lead acid 7 2Ah 12V Sealed lead acid 7 2Ah 12V Battery Quantity Backup time full load 9 min 5 min 5 min 5 min Recharge time 8 hours to 90 Dimensions i...

Page 27: ...x 480 x 430 6 7 x 21 6 x 16 9 170 x 550 x 430 Weight lbs kg net 50 22 7 90 41 110 50 125 57 Extended Run Time 19 Rack mount Models Capacity Input Connection Fixed power cord Hardwire terminals Output...

Page 28: ...are intended to limit the maximum amplitude of transient voltage surges on power lines to specified values They are not intended to function as surge arrestors The UPS is intended to be installed on t...

Page 29: ...__________________________________________________________ ______________________________________________________________________________ ______________________________________________________________...

Page 30: ......

Page 31: ......

Page 32: ...trackuserman2007rev2 Marathon Power Inc 2007 www marathon power com...

Reviews: